GT-HFM series constant temperature and humidity precision air conditioner specification |
Model GT-HFM-() | 35 | 40 | 50 | 55 | 60 | 70 | 80 | 90 |
Specification | Total cooling capacity | kW | 36.5 | 42.1 | 49.1 | 54.1 | 61 | 71.6 | 81.4 | 93.6 |
Sensible cooling capacity | kW | 33.8 | 38.4 | 44.3 | 49.8 | 55.5 | 65.1 | 74.7 | 85.1 |
Electric heating | kW | 15 | 18 | 18 | 18 | 24 | 24 | 30 | 30 |
Air volume 2* | m3/h | 10500 | 11500 | 13000 | 15500 | 18000 | 20500 | 22000 | 25000 |
Outlet air pressure 2* | PA | 75 | 75 | 75 | 75 | 100 | 100 | 125 | 125 |
Noise 3* | dB(A) | 56 | 58 | 58 | 58 | 58 | 58 | 60 | 60 |
Temperature control range and accuracy | ° C | 18~28, ± 1 |
Humidity control range and accuracy | % | 45~70, ± 5 |
Power | 3N-380V-50Hz |
Input power 4* | kW | 30 | 38.2 | 39.6 | 40.7 | 52.3 | 56.7 | 66.8 | 74.8 |
Indoor unit | Supply air fan | type | low noise centrifugal type |
capacity | kW | 2.2 | 3 | 3 | 4 | 5.5 | 7.5 | 7.5 | 11 |
Electrode humidifier | humidification volume | kg/h | 13 | 13 | 13 | 15 | 15 | 15 | 18 | 21 |
Electric heating | capacity | kW | 15 | 18 | 18 | 18 | 24 | 24 | 30 | 30 |
Evaporator type | Inner grooved copper tube and aluminum fin |
Air filter | primary efffect plate type filter |
Dimension | L | mm | 1800 | 1800 | 2000 | 2000 | 2000 | 2200 | 2200 | 2500 |
W | mm | 850 | 850 | 850 | 850 | 850 | 1080 | 1080 | 1200 |
H | mm | 2200 | 2200 | 2150 | 2150 | 2150 | 2350 | 2350 | 2450 |
Weight | kg | 580 | 610 | 710 | 750 | 820 | 900 | 980 | 1250 |
Outdoor unit | Model GT-( )*quantity | ##### | WL40*1 | ##### | WL55*1 | WL60*1 | WL70*1 | WL40*2 | WL50*2 |
compressor | type | Totally enclosed scroll type |
quantity | 1 | 2 | 2 | 2 | 2 | 2 | 4 | 4 |
condenser type | Inner grooved copper tube and aluminum fin |
Condensing fan | type | Low noise axial type |
capacity | kW | 0.75 | 0.55*2 | 0.55*2 | 0.55*2 | 0.75*2 | 0.75*2 | 0.55*4 | 0.55*4 |
Dimension | L | mm | 980 | 1880 | 1880 | 1880 | 1880 | 1880 | 1880 | 1880 |
W | mm | 980 | 980 | 980 | 980 | 980 | 980 | 980 | 980 |
H | mm | 1234 | 1080 | 1080 | 1080 | 1234 | 1234 | 1080 | 1080 |
Weight | kg | 250 | 320 | 400 | 400 | 450 | 500 | 320*2 | 400*2 |
Freon 5* | type | R22(R407C/R410A) |
control method | Out balance expansion valve |
Collecting pipe 6* | liquid pipe`s diameter | mm | 15.88 (12.7) | 15.88*2 (12.7*2) | 15.88*2 (12.7*2) | 15.88*2 (12.7*2) | 15.88*2 (12.7*2) | 15.88*2 (12.7*2) | 15.88*4 (12.7*4) | 15.88*4 (12.7*4) |
gas pipe`s diameter | mm | 34.9 (28.6) | 22.23*2 (19.05*2) | 28.6*2 (22.23*2) | 28.6*2 (22.23*2) | 28.6*2 (22.23*2) | 34.9*2 (28.6*2) | 22.23*4 (19.05*4) | 28.6*4 (22.23*4) |
| | | | | | | | | | | |
1. Cooling condition: Indoor dry bulb/wet bulb: 24/17° C; Outdoor dry bulb/wet bulb: 35/24° C; |
2. Air volume\static pressure are standard data, it can be designed by client | |
3. Noise data is measured 3 meters far away from the units | | | | |
4. The input power means the power consumption under max condtion | | | |
5. If freon is R410A or R407C, please noted it in the order | | | | |
6. The dimension in the brackets is for R410A`s collecting pipe | | | |