EDR-150-24 Meanwell 150W Single Output Industrial DIN Rail Switching Power Supply

Min.Order: 1
Product origin: Wenzhou, Zhejiang, China
Infringement complaint: complaintComplaint
US$ 19

Description

 

Features

 

  • Universal AC input / Full range

  • Protections: Short circuit / Overload / Over voltage/ Over temperature

  • Cooling by free air convection

  • Can be installed on DIN rail TS-35/7.5or 15

  • UL 508 (industrial control equipment) approved

  • EN61000-6-2(EN50082-2) industrial immunity level

  • 100% full load burn-in test

  • 2 years warranty

Applications

 

  • Industrial control system

  • Semiconductor fabrication equipment

  • Factory automation

  • Electro-mechanical apparatus

Description
  EDR-150-24 is one economical slim DIN rail power supply series, providing up to 156W at 230VAC input. This series is adapt to be installed on TS-35/7.5 or TS -35/15 mounting rails. The body is designed 40mm in width, which allows space saving inside the cabinets. The entire series adopts the full range AC input from 90VAC to 264VAC and conforms to EN61000-3-2(≤80% Load), the norm the European Union regulates for harmonic current.

  EDR-150-24 is designed with metal housing that enhances the unit's power dissipation. With working efficiency up to 87%,the entire series can operate at the ambient temperature between -20C and 60"C under air convection. It is equipped with constant current mode for over-load protection, fitting various inductive or capacitive applications. The complete protection functions and relevant certificates for industrial control . apparatus (UL508, TUV EN62368-1, and etc.) make EDR-1 50-24 a very competitive power supply solution for industrial applications.

 

SPECIFICATION

MODELEDR-150-24
OUTPUT DC VOLTAGE24V
RATED CURRENT6.5A/230VAC 5.2A/115VAC
CURRENT RANGE0~6.5A/230VAC 0~5.2A/115VAC
RATED POWER156W/230VAC 125W/115VAC
RIPPLE & NOISE (max.) Note.2150mVp-p
VOLTAGEADJ. RANGE24~28V
VOLTAGE TOLERANCE Note.3±1.0%
LINE REGULATION±0.5%
LOAD REGULATION±1.0%
SETUP, RISE TIME1500ms, 60ms/230VAC 3000ms, 60ms/115VAC at full load
HOLD UPTIME (Typ.)16ms/230VAC 10ms/115VAC at full load
INPUTVOLTAGE RANGE Note.690~264VAC 127~370VDC [DC input operation possible by connectingAC/L(+),AC/N(-)]
FREQUENCYRANGE47~63Hz
EFFICIENCY(Typ.)87%
AC CURRENT (Typ.)2.6A/115VAC 1.7A/230VAC
INRUSH CURRENT (Typ.)20A/115VAC 35A/230VAC
LEAKAGE CURRENT<1mA/ 240VAC
PROTECTIONOVERLOAD Note.7105 ~ 130% rated output power
Protection type : Constant current limiting, recovers automatically after fault condition is removed / 230VAC
105 ~ 150% rated output power
Protection type : Constant current limiting, recovers automatically after fault condition is removed / 115VAC
OVER VOLTAGE29~33V
Protection type : Shut down o/p voltage, re-power on to recover
OVER TEMPERATUREShut down o/p voltage, re-power on to recover
ENVIRONMENTWORKING TEMP.-20ºC~+60ºC(Refer to "Derating Curve")
WORKING HUMIDITY20~95% RH non-condensing
STORAGE TEMP., HUMIDITY-40~+85 , 10~95% RH
TEMP. COEFFICIENT±0.03% /ºC(0 ~ 50 )
VIBRATIONComponent:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X,Y, Z axes; Mounting: Compliance to IEC60068-2-6

SAFETY&EMC

(Note 4)

SAFETYSTANDARDSUl508,TUV EN62368-1, , BSMI CNS14336-1 approved;(meet EN60204-1) 
WITHSTAND VOLTAGEI/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
ISOLATION RESISTANCEI/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25 / 70% RH 
EMC EMISSIONCompliance to EN55032 (CISPR32) ClassA, EN61000-3-2, ClassA( 80% Load), EN61000-3-3, ClassA
EMC IMMUNITYCompliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2 (EN50082-2), heavy industry level, criteriaA, EAC TP TC 020
OTHERSMTBF472.5K hrs min. MIL-HDBK-217F (25ºC)
DIMENSION 40*125.2*113.5mm (W*H*D)
PACKING0.6Kg; 20pcs/13Kg/1.16CUFT
NOTE1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 C of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47ut pall capacitor.
3. Tolerance ; includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be nstalledl into a final equipment. The final equipment must be re-confirmed that it sil mets EMC directives.
5. Intallation clearances : 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanenty with full power, In case the adjacent device is a heat source, 15mm clearance is recommended.
6. Derating may be needed under low input voltage. Please check the derating curve for more details.
7. Hiccup mode al 90~100VAC, recovers automatically atter fault condition is removed,
8. The ambient temperature derating of 3.5"C/1000m with fanless models and of 5C/1000m with fan models for operating altude higher than 200m(6500t).

 

Mechanical Specification(mm)