Input & Output voltage | Capacity |
| |
220VAC output design | |
24VDC-220VAC | 1-5KVA |
48VDC -220VAC | 1-6KVA & 8KVA&10KVA |
110VDC -220VAC | 1-6KVA & 8KVA&10KVA |
220VDC-220VAC | 1-6KVA & 8KVA&10KVA |
120VAC output design | |
24VDC-120VAC | 1-5KVA |
48VDC -120VAC | 1-6KVA |
110VDC -120VAC | 1-6KVA |
Brand | IDEALPLUSING | |
Model | IPS-DTA3000-24 | |
Rate Capacity(KVA) | 3KVA | |
Rate power(W) | 2400W | |
DC Input | Rate input voltage | 24VDC |
Rate input Current | 117A | |
Shut down voltage range | 20V-30.5VDC | |
Start-up voltage range | 21.5V-29.5VDC | |
Reflect noise current | ≤10% | |
AC Input | Allow bypass voltage | 220VAC |
Bypass switch time (ms) | ≤5ms | |
AC Output | Rated capacity (VA) | 3KVA |
Rated output power (W) | 2400W | |
output voltage and frequency | 220VAC | |
Output voltage precision | 220±10VAC | |
Output frequency precision | 50±0.1% Or 60±0.1% HZ | |
Waveform | Pure sine wave | |
Total harmonic distortion | ≤3% (linear load) (THD) | |
Dynamic response time | 5% (load 0←→100%) | |
Power factor (PF) | 0.8 | |
Overload capacity | 100%-120% 60s121%-150% 10s | |
Inversion efficiency (80% resistive load) | ≥85% | |
By-pass conversion time (ms) | ≤5ms | |
Operating environment | Dielectric strength (input and output) | 1500VAC, 1 minute |
Noise (1m) | ≤40dB | |
Operating environment temperature | -20ºC~+50ºC | |
Humidity | 0~90%, no moisture condensation | |
Operating altitude (m) | ≤2000 | |
Indication | LCD display | Input and output voltage, frequency, output current, temperature, percentage, etc. |
inverter status | Normal mains, normal inversion, battery under-voltage and output overload | |
Mechanical size | Standard rack (Depth * Width * Height) (mm) | 482*368*88MM , 14KG |
Protection function | Input under-voltage and over-voltage, output overload and short circuit protections, etc. |
NO | Model Name | Input Voltage VDC | Output Voltage VAC | Output Capacity KVA | Machine Size(MM) NW: KG |
#17 | IPS-DTA500-48(1U) | 48VDC | 110/120VAC | 0.5KVA | 482*300*44 5KG |
#18 | IPS-DTA1000-48(1U) | 48VDC | 110/120VAC | 1KVA | 482*300*44 5KG |
#19 | IPS-DTA1000-48(2U) | 48VDC | 110/120VAC | 1KVA | 482*335*88 8KG |
#20 | IPS-DTA2000-48(2U) | 48VDC | 110/120VAC | 2KVA | 482*368*88 13KG |
#21 | IPS-DTA3000-48(2U) | 48VDC | 110/120VAC | 3KVA | 482*368*88 15KG |
#22 | IPS-DTA4000-48(4U) | 48VDC | 110/120VAC | 4KVA | 482*440*177 25KG |
#23 | IPS-DTA5000-48(4U) | 48VDC | 110/120VAC | 5KVA | 482*440*177 27KG |
#24 | IPS-DTA500-48(1U) | 48VDC | 220/230VAC | 0.5KVA | 482*300*44 5KG |
#25 | IPS-DTA1000-48(1U) | 48VDC | 220/230VAC | 1KVA | 482*300*44 5KG |
#26 | IPS-DTA1000-48(2U) | 48VDC | 220/230VAC | 1KVA | 482*335*88 8KG |
#27 | IPS-DTA2000-48(1U) | 48VDC | 220/230VAC | 2KVA | 482*300*44 5KG |
#28 | IPS-DTA2000-48(2U) | 48VDC | 220/230VAC | 2KVA | 482*368*88 10KG |
#29 | IPS-DTA3000-48(1U) | 48VDC | 220/230VAC | 3KVA | 482*300*44 5KG |
#30 | IPS-DTA3000-48(2U) | 48VDC | 220/230VAC | 3KVA | 482*368*88 10KG |
#31 | IPS-DTA4000-48(2U) | 48VDC | 220/230VAC | 4KVA | 482*368*88 13KG |
#32 | IPS-DTA5000-48(2U) | 48VDC | 220/230VAC | 5KVA | 482*368*88 14KG |
#33 | IPS-DTA6000-48(2U) | 48VDC | 220/230VAC | 6KVA | 482*368*88 15KG |
#34 | IPS-DTA8000-48(4U) | 48VDC | 220/230VAC | 8KVA | 482*440*177 25KG |
#35 | IPS-DTA10000-48(4U) | 48VDC | 220/230VAC | 10KVA | 482*440*177 26KG |