ADW series rail type multi-loop power meters are mainly used for measuring the full electric parameters of multiple three-phase circuits, up to four three-phase loop current inputs can be connected simultaneously. It can measure voltage and current, power, power factor, phase angle, unbalance, harmonic and other parameters.
Click the above photo to see the details |
ADW200 | ADW210 | ADW220 |
RS485 | RS485+LCD | RS485+LORA |
MK | MTL | AWT100 |
Digital Input: 12 Channels DI Digital Output: 4 Channels DO | Temperature: 12 External NTC Temp. Measurement; -20ºC~+100ºC; Accuracy ± 2ºC Residual Current: 4 Channels Residual Current Measurement; 10~3000 mA; Accuracy 1% (Class 1) | Downlink: RS485; Uplink: WiFi, 4G, 2G, NB, Lora, LoraWAN, Ethernet, GPS, Profibus |
Split-core Current Transformer Matched with ADW2xx Series | Dimension(mm) | Perforation size (mm) | |||||
W | H | D | M | N | φ1 | φ2 | |
AKH-0.66/K-φ 10N | 27 | 44 | 32 | 25 | 36 | 10 | 9 |
AKH-0.66/K-φ 16N | 31 | 50 | 36 | 27 | 42 | 16 | 17 |
AKH-0.66/K-φ 24N | 39 | 71 | 46 | 36 | 52 | 24 | 23.5 |
AKH-0.66/K-φ 36N | 42.5 | 82 | 58 | 40 | 56 | 36 | 35 |
Specification | Input Current | Output Current | Hole Size (mm) for Conductor | |
D10 | 5A | 1.25mA | 10mm | |
D16 | 100A | 20mA | 16mm | |
D24 | 400A | 100mA | 24mm | |
D36 | 600A | 100mA | 36mm |
Function | Description | |||
Energy Measurement | kWh (positive and negative) | |||
kvarh (positive and negative) | ||||
A,B, C three-phase positive kWh | ||||
Electric Parameter | U, I, P, Q, S, PF, Hz | |||
Harmonic | 2-31st voltage and current harmonic | |||
Communication | RS485 (MODBUS-RTU); baud rate 1200~38400 | |||
Key Programming | 4 keypads to set communication and parameters | |||
Display | LCD display, 8 digits | |||
LED Alarm | Over-voltage, over-current, interruption phase | |||
Data Log | Maximum demanded kWh and the time it happened. | |||
SOE | up to 200 pcs, record on-off status of DO/DI | |||
Pulse Output | Active optocoupler pulse output with open collector | |||
Multi-rate/Tariff | 4 time zones & 12 time periods |
Expanded Module | Description | |||
AWT100 Communication Module | 4G (Global general module) | |||
2G | ||||
LoRaWAN (868 MHz, 923MHz) | ||||
LoRa (460~510 MHz) | ||||
NB-IoT | ||||
-MK Switch Module | 12 × DI (input) | Dry contact input with built-in power supply | ||
4 × DO (output) | Relay normally open contact output; rating AC 250V/3A ,DC 30V/3A | |||
Power Supply | DC 12V;consumption:≤1W;RJ45 interface | |||
Communication | RJ45 interface; MODBUS-RTU (communication with main body) | |||
-MTC Temperature & Residual Current Measuring Module | Temperature Measurement | -20ºC~+100ºC | ||
Residual Current Measurement | 10~3000 mA | |||
Accuracy | Temperature:± 2ºC; Residual Current:1% (Class 1) | |||
Power Supply | DC 12V;consumption:≤1W;RJ45 interface | |||
Communication | RJ45 interface; MODBUS-RTU (communication with the main body) |
Parameters | Description | |||
Input | Voltage | AC 3×220V/380V | ||
Overload: 1.2 times of rated value (continuous); 2 times of rated value / 1s | ||||
Power consumption:≤ 0.5VA | ||||
Current | AC 5A,100A,400A,600A;(external open-type CT) | |||
Overload: 1.2 times of rated value (continuous); 10 times of rated value / 1s | ||||
Power consumption:≤ 0.5VA | ||||
Frequency | 45~65Hz | |||
Measuring Accuracy | Voltage&Current | Class 0.5 | ||
Active Power | Class 1 | |||
Reactive Power | Class 2 | |||
Frequency | 0.05Hz | |||
2~31st harmonic | ± 1% | |||
Auxiliary Power | AC/DC 85~265V;consumption≤10VA; | |||
EMC | Better than grade 3 | |||
Safety | Withstand Voltage | >AC 2000V/1min | ||
Insulation Resistance | >100MΩ | |||
Environment | Working Temperature | -20ºC~+60ºC | ||
Storage Temperature | -40ºC~+70ºC | |||
Humidity | ≤95% (No condensation) | |||
Altitude | ≤2500m |