Acrel AC Three Phase Data Center Electric Monitor Device with CE Certification

Min.Order: 1
Product origin: Shanghai, China
Infringement complaint: complaintComplaint
US$ 91

Description
Type
Function
AMC16MA
Three Phase: 2 Channels Inlet I, U, P, Q, EP, EQ, S
Single Phase: 36 Channels Outlet (Three Phase 12 Channels Outlet) I, U, P, Q, EP, EQ
1DO, RS485 (Modbus-RTU)
AMC16MAH
Measure the Total Three Phase Incoming Line Voltage, Two Three-phase Incoming Lines I, kW, kvar, cosΦ, kWh, kvarh (Required Configure AKH-0.66W 100A/20mA Current Transformer); Measure Incoming Line Voltage, Incoming Line Current, Outgoing Line Current 2-15 Sub-Harmonics and Total Harmonics; 1 RS485 Communication; 1DO, AC220V Power Supply
AMC16Z-ZA
A+B Independent 2 Channels Three-phase Inlet U, I, P, Q, S, PF, EP, EQ, UN to PG, Neutral Current 2-63rd Harmonic of Voltage and Current 6 Channels Passive Switching Input 2 Channels Switching Output RS485 (Modbus-RTU) Communication
AMC16Z-ZD
Measurement of A+B Independent 2-way DC Bus Voltage, Current, kW, kWh, 6DI+2DO+1RS485 (Modbus-RTU)
AMC16Z-KA
A+B Independent 2 Way Unilateral 24 Active Switch States
AMC16Z-KD
A+B Independent 2 Way Unilateral 24 Passive Switch States
AMC16Z-FAK24
Measure A+B Two-way AC Outlet, Total 24 Branch Full Electric Parameter and Switch  Value Status, 1 RS485 (Modbus-RTU)
AMC16Z-FAK48
Measure A+B Two-way AC Outlet, Total 48 Branch Full Electric Parameter and Switch Value Status, 1 RS485 (Modbus-RTU)
AMC16Z-FDK24
Measure A+B Two-way DC Outlet, Total 24 Branch Full Electric Parameter and Switch Value Status, 1 RS485 (Modbus-RTU)
AMC16Z-FDK48
Measure A+B Two-way DC Outlet, Total 48 Branch Full Electric Parameter and Switch Value Status, 1 RS485 (Modbus-RTU)

Technical Parameter
Value
Distribution System
AC
Measurement of Electrical Parameters
A+B Independent 2 Channels Three-phase Inlet U, I, P, Q, S, PF, EP, EQ, UN to PG, Neutral Current 2-63rd Harmonic of Voltage and Current 6 Channels Passive Switching Input 2 Channels Switching Output RS485 (Modbus-RTU) Communication
Voltage
Nominal
220VAC
Range
±20%
Overload
2 Times Lasting 1 Second (Instantaneous)
Current
CT
XXA/5A
Range
0-120%
Overload
1.2 Times (Continuous), 10 Times (Instantaneous)
Input Frequency
45-65Hz
Accuracy
Class 0.2 (U/I)  Class 0.5 (P/EP)  Class 1 (Q/EQ)
Insulation Resistance
100MΩ
Switch Output
2 Channels (3A 250VAC / 3A 30VDC)
Switch Input
6 Channels
Communication
RS485 (Modbus-RTU)
Installation
Din 35mm

Product Tag:
Related categories: