High quality/High cost performance 125A 250A Power Magnetic Contactors Electrical 160A AC Contactor

Min.Order: 1
Product origin: Wenzhou, Zhejiang, China
Infringement complaint: complaintComplaint
US$ 46.67

Description

Product Information:

CKJ5 Vacuum Contactor 220V 380V 440V 690V 1140V 80A 125A 160A 250A 400A 500A 630A 3 pole Vacuum Contactor

 

Application 

CKJ5 series AC Vacuum Contactor is designed for long-distance making and breaking in circuit, frequency starting and controlling AC motor in the power system with AC 50 Hz-60Hz, rated operating voltage to 1140V. It also can be formed with thermal relay and all kinds of protection apparatus, as electromagnetic starter, especially applies to explosion electromagnetic starter and all sorts of power control equipment. It may apply to the department of mine, metallurgy, petroleum, chemical industry, power, communication transportation and so on.

The contactor conforms to IEC 60947-4-1,GB/T 14048.4 and JB/TN 7122 standard,the main performance indicators have reached the international level.
"Y"means this product has coil operation mechanism type and permanent magnet operation mechanism type.Coil operation mechanism type is normally used.Customers can choose the suitable type according to the application.

 

Normal working and installation conditions

Ambient temperature: -25ºC~+40ºC

Altitude: ≤2000

Humidity: Relative humidity on daily average less than 95%, on monthly average less than 90%.

Water vapor pressure on daily average less than 2.2kPa, on monthly average less than 1.8kPa.

No normally violent vibration.

 

Main technical parameter

ModelCKJ5-160/1140CKJ5-250/1140CKJ5-400/1140CKJ5-630/1140
Main
Circuit
Rated working current (Ie)80A, 125A, 160A200A, 225A, 250A400A500A, 630A
Rated working voltage (Ue)1140V
Rated frequency (fr)50/60Hz
Rated making capacity (100 times)10Ie
Rated breaking capacity (25 times)8Ie
Limit breaking capacity (3 times)2000A4500A4500A6000A
Withstand Voltage (power frequency)4200V
Control circuitRated voltage (Us)AC. 220/380V, DC. 110/220V, or other Customerized control voltage
Withstand Voltage (power frequency)2000V
Rated power (Ps) electric holdingabsorbing≤600VA
holding≤50VA
Auxiliary circuitForm2a+1b4a+3b
Withstand Voltage (power frequency)2500V
Rated valueAC 380V/5A, DC 380V/1A
Main
Contact
Parameter
fixed - moving contact distance1.8±0.2mm2.0±0.2mm
Overtravel1.0±0.2mm
Final pressure30±3N78±7.8N117.6±11.8N196±19.6N
Rated operating frequencyLong-term (AC-3)600 times/h
Long-term (AC-4)300 times/h
Short-term3000 times/h2000 times/h
Mechanical endurance3,000,000 times
Electrical enduranceAC-3600,000 times
AC-460,000 times20,000 times5,000 times
Mechanical characteristicsClosing time≤200ms
Original opening time≤160ms
3-phase synchronism≤3ms
Closing tripping≤10ms

 

Overall and installation dimension

Product Tag:
Related categories:
Scroll to Top