Item | ZFP500 | ZFP1000 | ZFP2000 | ZFP3000 | |
Dry powder filling amount(Kg) | 500 | 1000 | 2000 | 3000 | |
Fire class | BC/ABC | ||||
Supercharging time(s) | ≤20 | ||||
Spraying time(s) | ≥60 | ||||
Residual powder ratio | ≤10% | ||||
Operating temperature range(ºC) | -20~+50 | ||||
System boot mode | Automatic, manual, mechanical emergency | ||||
Dry powder tank | Volume(m3) | 0.75 | 1.4 | 2.2 | 3.5 |
Design pressure(MPa) | 1.6 | 1.8 | 1.6 | ||
Working pressure(MPa) | 1.5 | 1.6 | 1.55 | ||
expellant gas cylinder | Gas type | N2 | |||
Volume(L) | 70 | ||||
Number of cylinders | 2 | 4 | 9 | 13 | |
Filling pressure (+20ºC)MPa | 13.5 | ||||
Starting cylinder | Gas type | N2 | |||
Volume(L) | 8 | ||||
Filling pressure (+20ºC)MPa | 6.0 |