Rpm100/100c Power Meter Multi Meter Power Quality Analyser Network Analyzer

Min.Order: 1
Product origin: Foshan, Guangdong, China
Infringement complaint: complaintComplaint
US$ 214 ~ 589

Description

Product Description


Measurements
Measurements:VL-L, VL-N, I, In, Iz, Cos , Pf, Hz, W, ∑W, Va, ∑Va, Var, ∑Var, Kwh, Kvarh, V-THD, I-THD, 1-128th harmonic ,
   system running hours,% voltage unbalance, % system load,% system leakage,frequency;Fast simultaneous sampling on all
8 channels at 1024 samples/cycle(True RMS measurements)
For single-phase, two-phase, three-phase system
4 voltage channel input, voltage direct connection up to 690VLL or through PT for MV and HV systems.
5 current input: 0.05-5.5A
4th current channel dedicated for neutral current measurements, the current measuring range (CT primary and secondary )
   
 can be programmed together with the main three-phase channels
5th current channel reserved for Earth Leackage monitoring (ZCT input) according to IEC60755 & IEC61140
Suitable for 45-65Hz systems
All measured voltage characteristics certified according to IEC/EN61000-4-30:2015 Ed.3, Class A
4 quadrants energy measurement , 4 tariffe energy measurement and  monthly energy calculation
Transients detection >25us, Detection of events >10ms
Voltage flicker measurement, and waveform capture
Maximum, minimum and demand for U, I, P, Q, S in hours, days, months
Phase diagram for voltage, current Detects CT wiring errors 

Data storage & recordings
Voltage and current sag/swell and transient event capture
Waveform acquisition and capture of voltage and current
Automatic fault analysis and report: Phase sequence, Phase fault, Voltage over, Voltage under, Sag/swell, Frequency over,
   Current over, Short circuit, Leakage,Voltage harmonic, Current harmonic(according to IEC62606: 2013)
Alarm event log: VL-L, VL-N, I, In, ΣW, ΣVar, THD-U, THD-I...
Monthly electricity statistics
Built in 256M flash memory &32MB RAM for event and transient memory
Micro SD(support 32GB) for fault logger and data logger
Data recorded in standard excel file formats for further EN50160 analysis

Clock & language
Real time clock with integrated backup rechargeable battery
English, Chinese (traditional & simplied) or other

Communication
RS485 port of Modbus RTU
Ethernet port of Modbus TCP/IP+web server

Function module (only one can be selected)
7 digital input+2 analog output (4-20mA) for V1, V2, V3, V12, V23, V31, I1, I2, I3
Ethernet (Modbus TCP), web server+2 digital input+2 relay output (remote or alarm)
LoRa wireless (Private protocol)+2 digital input+2 relay output (remote or alarm)
RS-485 interface (Modbus RTU)+2 digital input+2 relay output (remote or alarm)
WIFI wireless+2 digital input+2 relay output (remote or alarm)

Product Parameters

Auxiliary Supply
Operating voltage (Un)85···265 VAC 50/60Hz 10W / 100-285VDC/24-48VDC(depend on order)
Power consumption10VA max
Measurement input
Voltage inputs for direct connection:Phase-neutral(L-N): max 400V RMS CAT III
Input impedance(for direct voltage inputs):>4MΩ
CT inputs:max 5.5A RMS
CT inputs overload capacity:max 10A
CT inputs Self-consumption :<0.2VA
Accuracy
Three phase voltage:± 0.2%
Currents:± 0.2%
Powers:± 0.3%
Powers factor:± 0.3%
Frequency:± 0.02%
Harmonics:Class 1 (IEC/EN61000-4-7)
Active energy:Class 0.2S (IEC/EN 62053-22)
Reactive energy:Class 0.5S (IEC/EN 62053-23)
Insulation
Insulation voltage
3kV for 1 min., 50Hz
Display
Display type
3.2inch 240x160 pix LCD/3.5 inch 320x240 color TFT LCD
I/O
Digital inputs:
Active dry contact
Digital outputs:
2 Relay N/O 220VAC 5A
Analog outputs:
4-20mADC / max load 500Ω
Pulse output:
12-30VDC Max.50mA, Min. 50msec pulse width
Memory 
Recording memory:
max 32 GB SD (TF)
Communication
Ethernet port:
Auto MDIX Rj45 10/100 Base Ethernet
RS-485 port:
1 optoisolated, 4800-57600
Protocols:
HTTP, HTTPS, Modbus RTU/TCP
Environmental conditions
Opterating temperature:
-10···+55°C
Storage temperature:
-25···+75°C
Relative humidity:
95% max without condensing
Altitude:
max 2000m AMSL
Installation & use:
Internal
Mechanical characteristics
Mounting:
Panel mount 96x96mm(The panel cut-size 92*92mm)
Size:
Front(WXH)96x96mm, Rear (HxD) 90x70mm
Degree of protection:
IP40(optional IP54) on front, IP20 housing and terminals
Weight:
400g
Standard compliance
reference standard:
IEC61010-1; IEC61557-1;IEC61557-12; IEC61326-1;IEC62053-21;
IEC62053-22; IEC62053-31; IEC60068-2-1; IEC60068-2-30;
IEC60364-5-52; IEC61000-3-2; IEC61000-3-3; IEC61000-4-2;
IEC61000-4-3; IEC61000-4-4; IEC61000-4-5; IEC61000-4-6;
IEC61000-4-8; IEC61000-4-11; IEC61000-4-30

Detailed Photos

 

Installation Instructions

Company Profile

Scroll to Top