The AOUE1+2 line is a group of Class l+l Surge Protective Devices. They are intended as a protecti-on againstindirectand low intensity direct hits of lightning strokes. n standard three phase TN-C grid, they provides protection to LPL Ill, vrequirements given in EN 62305 with totallightning current introduced into electrical installation of 37.5 kA and totallightningstroke current 75 or 100kA based on physical conguration and mutual position of grounding point oflightning rod, groundingpoint of the electrical installation and place of SPD installation.
Poles | 1+0, 2+0, 3+0, 4+0, 1+1, 3+1 | 1+1, 3+1 | |
(L-N/PE/PEN) | (X+1 NPE) | ||
Standards | EN 61643-11 | ||
Category lEC/VDE | Type1+2(Classl+ll,B+C,T1+T2) | ||
Technology | MOV (Varistor) | GDT(Spark-gap) | |
Reference test voltage | 250VAC | ||
Max.continuous operating voltage | 275VAC | 255VAC | |
Nominal frequency | 50/60Hz | ||
Nominal discharge current(8/20) In | 25 kA per pole | 50 kA per pole | |
Max.discharge current(8/20) Imax | 50 kA per pole | ||
Lightning impulse current(10/350) limp | 8 kA per pole | 12.5 kA per pole | 50 kA per pole |
Voltage protection level @In | <1.5kV | ||
Response time | <100 ns | ||
FN-PE follow current interrupting rating | - | 100A | |
Max.Permissible Strength of Backup Fuse | 160A gL/gG | - |