Transmission Power Station Double Stage Vacuum Transformer Oil Purifier System

Min.Order: 1
Product origin: Chongqing, China
Infringement complaint: complaintComplaint
US$ 10000 ~ 30000

Description

ZYD-I Series
Double-Stage Vacuum Transformer Oil Purifier

 

Application

ZYD-I machine is specially designed for on site use to completely regenerate insulating oils in energized or de-energized transformers. It not only provides regular oil purification including degassing, drying and particulate removal but also removes acidity, sludge, other soluble oil decay products, and improves color. For special application, the system also can be mounted on a leak proof base or be installed and operated on a trailer.

Features

1. For special application, the operation can be controlled by P.L.C (Programmable Logic Controller) (ZYD-I-A Series).
2. Unique vacuum dehydration, degassification and regeneration system, adopt stereo-evaporation technology. Duplex 3D stereo-evaporation, eliminating the liquid water quickly
3. UK g technology by which the trace water that is show chain, such as dissolved water, can be removed effectively.
4. Advanced infrared liquid-level automatic control system to accomplish fully automatic control.
5. Can be applied for vacuum oiling and drying power transmission equipment.
6. Special additives for depolarization can recover oil color of aged transformer oil to new.


Working Principle

The insulating oil is conveyed into the degassing tank by means of pressure difference. Oil is indirectly heated by the heater, thus avoiding hot spots and over-swinging of the pre-selected operating temperature. The special degassing system and geometry with several stages in degassing tank creates a large oil surface and a resulting thin film for most effective maximum degassing. The treatment with a lower end vacuum (-0.08 to -0.095 MPa) guarantees, among others, that no light fractions are evaporated in the insulating oil, whereby the required characteristics of the oil are not changed.

The oil level regulation in the degassing tank assures a continuous oil flow-through in the plant, thus resulting in an optimised degassing of the oil.

After degassing and dehydration under vacuum, the oil is conveyed by means of a specially sealed and frequency controlled pump into regeneration system. Then oil through the fine filter and out of the plant.


Technical Parameter
 
ParameterUnitZYD-I-30ZYD-I-50ZYD-I-100ZYD-I-150ZYD-I-200ZYD-I-250ZYD-I-300
Flow rateL/h1800300060009000120001500018000
Working vacuumMPa-0.08~-0.099
Working pressureMPa≤0.3
Temperature rangeºC20 ~ 80
Power 3 ph 380V 50Hz (Or as needed)
Working noisedB(A)75757575808080
Heating powerkW303045607590120
Total powerkW35.537.552.571.486.5102.5135
Oil Inlet/Outletmmφ25φ32φ42φ50φ50φ60φ60
WeightKg60080010501400180020002200
OverallLmm1050110012001450160018001900
 Wmm750800950950110012001200
 Hmm1350140015001650180019001900
 
 
ItemUnitAfter treatment
Breakdown VoltagekV≥75
Moisture contentPPM≤3
Gas content%≤0.1
Impurity sizemicron≤1 (no free carbon)
IFTdynes/cm≥40
Acid valuemg KOH/g≤ 0.03
Dielectric loss factorstgδ(90ºC)≤0.001