NO. | Type of Device | Direct Type Fire Detecting Tube CO2 Fire Suppression Device | Indirect Type Fire Detecting Tube CO2 Fire Suppression Device | Direct Type Fire Detecting Tube FM200 Fire Suppression Device |
1 | Device model | WZ-Q/T-EZ6-XJ60 | WZ-Q/T-EJ42-XJ60 | WZ-Q/T-QZ3-XJ60 |
2 | Storage Pressure (20ºC) | 5.17Mpa | 5.17Mpa | 2.5Mpa |
3 | Max. Working Pressure | 12.1Mpa | 12.1Mpa | 4.2Mpa |
4 | Min. Agent Needed for A Unit | 2.5kg/m³ | 1.5kg/m³ | 0.7kg/m³ |
5 | Max Agent Capacity | 6kg | 42kg | 3kg |
6 | Max. Length of Fire Tube | 25m | 25m | 20m |
7 | Max. Length of Release Tube | -- | 12m | -- |
8 | Max. Filling Rate | 0.6kg/L | 0.6kg/L | 1.12kg/L |
9 | Working temperature | 0ºC~49ºC | 0ºC~49ºC | 0ºC~50ºC |