13.2kv 20kVA Single Phase Transformer Pole Mounted Type for Outdoor Using

Min.Order: 6
Product origin: Nantong, Jiangsu, China
Infringement complaint: complaintComplaint
US$ 1100 ~ 3500

Description

Product Description

Single phase pole mounted transformers designed and produced by Daelim are normally used for stepping utility distribution voltages(from 2400V to 34500V) down to lower utilization voltages. Although some are used for stepping down to commercial and industrial voltages such as 277V, 240/480V, 2400V and 4800V, most are used for stepping down to the single phase voltage of 120/240V.

Product Parameters

 
Technical Data For Single Phase Pole Mounted Transformer Conventional Type
Rate powerHigh voltageLow voltageNo load losses(w)On load losses(w)Weight(kg)
10kva
34500/19920V
13800/7957V
13200/7620V
12470/7200V
or others
120-240V
240-480V
347V
600V
36120150
15kva50195210
25kva80290258
37.5kva105360340
50kva135500395
75kva190650480
100kva210850583
167kva3501410680
Technical Data For Single Phase Pole Mounted Transformer CSP Type
Rate powerHigh voltageLow voltageNo load losses(w)On load losses(w)Weight(kg)
10kva
34500/19920V
13800/7957V
13200/7620V
12470/7200V
or others
120-240V
240-480V
347V
600V
50120150
15kva65195205
25kva105290245
37.5kva140360335
50kva180500370
75kva250650505

These transformers also used for small substation, miscellaneous applications and can serve to step up voltages.Daelim designs and produces single phase in two types: single phase pole mounted conventional transformer and completely self protected(CSP) transformer. Power rating up to 167kVA.

Daelim's single-phase fully complies with or even exceeds international standards such as ANSI/IEEE, CSA, and DOE. Single-phase has ul/cul, CSA, IEEE and other certificates. It has been exported to North America, Central and South America and other markets in large quantities.

Conventional Type

 

The transformer is cylinder sealing structure. Each one is fixed with grounding devices, hooks, sup porting lugs which conforms to ANSI standard, and one or two high voltage bushing on the cover, low voltage bushing on the wall of the tank and eyebolt,connecting terminals. The tap changer should be adjusted basing on the instruction after the power off.

 

CSP Type

This type of transformers are CSP type, which can protect itself from thunder and lighting, short circuit and protect the transiting and distribution line from current failure because of self-malfunction.
Except from some similarities such as cylinder tank, hooks, lifting lugs, grounding devices, nameplates, core and winding with the conventional type. This type of transformers have characteristics and devices as follows:
1) One or two high voltage bushings are on the cover with fuse.
2) One or two arresters are installed on the wall of the tank, whose top end is near to the high voltage bushing, and connected to the bushing by a copper strip. One secondary breaker switch is above the winding inside the tank, and here are operating handle,overload reset and signal light.
3) Low voltage bushing is educed from the wall of the tank, grounding device is fixed to position X2. One end of the single
bushing leads out through the high voltage bushing, the other end is ground connection.
4) All units are built in accordance with ANSI/IEEEC57.12.20, CSA C2.1-06,CSA C2.2-06 and etc.

Optional Accessories

Single phase pole mounted transformer
1. Surge Arrester
2. Protective Link
3. Current Limiting Fuse
4. Low Voltage Circuit Breaker
a. Circuit Breaker Emergency Control
b. Signal Light
5. Protecto Combo
6. Tap Changer
7. Dual Voltage Swithc
8. Tank Pressure Relief

Projects cases

 

Certifications

 

 
Product Tag:
Related categories:
Scroll to Top