Range | -0.1MPa...0kPa~10kPa...100MPa | ||
Fluid material | Standard: 316L stainless steel ceramics, typical: khashi alloy or gold plated diaphragm | ||
Display range | -1999~9999 | ||
Accuracy | 0.1% (custom), 0.25% (typical), 0.5% (maximum) | ||
Temperature Drift | ≤±0.05%FS/°C (temperature range -20~85°C) | ||
Zero point | ≤±0.02%FS/°C (Typical), ≤±0.04%FS/°C (Max) | ||
Full point | ≤±0.02%FS/°C (Typical), ≤±0.04%FS/°C (Max) | ||
Compensation temperature | 0°C~50°C(≤100kPa), -10°C~70°C(>100kPa) | ||
Heat return difference | ≤±0.5%FS | ||
Filling flfluid | 1. Silicone oil 2.Synthetic oil or sanitary oil | ||
Response time | Current output max. 2ms, Voltage output max. 10ms | ||
Storage temperature | -40°C~125°C | ||
Medium temperature | -30°C~300°C | ||
Mechanical impact | 100g/1ms | ||
Mechanical vibration | Max. 20g: 15~2000Hz | ||
Power supply | 12 ~ 36VDC (Power consumption of 30mA) | ||
Output Signal | Analog output: 4mA~20mA (superimposable HART protocol).0V~10V Digital output: RS485 Control output: Switch: 2 way, analog quantity: 1 way | ||
Load error | < 0.5% | ||
Protection leve | IP65/IP67 |