CNC Electric 32A 250VDC 63A 6ka 1p Breakers MCB DC Circuit Breaker

Min.Order: 200
Product origin: Wenzhou, Zhejiang, China
Infringement complaint: complaintComplaint
US$ 2.19 ~ 9.05

Description

YCB8-125 PV Photovoltaic DC MCB CIRCUIT BREAKER






Product Description

General
The rated operating voltage of YCB8-125PV series DC miniature circuit breakers can
reach DC1000V, and the rated operating current can reach 125A, which are used forisolation, overload and short circuit protection.
It is widely used in photovoltaic,
industrial, civil, communication and other systems, and can also be used in DCsystems to ensure the reliable operation of DC systems.
Standards: IEC/EN 60947-2.

 
Features
Modular design, small size;
Standard Din rail installation, convenient installation;
Overload, short circuit, isolation protection function, comprehensive protection;
Current up to 125A, 4 options;
The breaking capacity reaches 6KA, with strong protection capacity;
Complete accessories and strong expansibility;
Multiple wiring methods to meet various wiring needs of customers;
The electrical life reaches 10000 times, which is suitable for the 25-year life cycle of
photovoltaic.
StandardsIEC/EN 60947-2
Number  of  poles1P2P3P4P
Rated current of shell frame grade125
Electrical performance 
Rated working voltage Ue(V DC)2505007501000
Rated current In(A)63,80,100,125
Rated insulation voltage Ui(V DC)500VDC  per  pole
Rated  impulse voltage Uimp(KV)6
Ultimate breaking capacity Icu(kA)Pv:6    PVn:10
Operation breaking capacity Ics(KA)PV:Ics=100%Icu      PVn:Ics=75%Icu
Curve  typeli=10ln(default)
Tripping typeThermomagnetic
Service life
(time)
Mechanical20000
ElectricalPV:1000      PVn:300
PolarityHeteropolarity
Inline  methodsCan be up and down into the line
Electrical accessories 
Auxiliary contact 
Alarm  contact 
Shunt  release 
Applicable environmental conditions and installation
Working  temperature(ºC)-35~+70
Storage  temperature(ºC)-40~+85
Moisture resistanceCategory  2
Altitude(m)Use with derating above 2000m
Pollution degreeLevel 3
Protection  degreeIP20
Installation environmentPlaces without significant vibration and impact
Installation categoryCategory I III
Installation methodDIN35 standard rail
Wiring capacity2.5-50mm²
Terminal  torque3.5N-m