SPECIFICATION | |||||||||
OUTPUT | |||||||||
MODEL | ADD-155A | ADD-155B | ADD-155C | ||||||
Output number | CH1 | CH2 | CH3 | CH1 | CH2 | CH3 | CH1 | CH2 | CH3 |
DC voltage | 13.8V | 5V | 13.3V | 27.6V | 5V | 27.1V | 54 V | 5 V | 53.5 V |
Rated Current | 9.5A | 3A | 0.5A | 4.5A | 3A | 0.5A | 2.3A | 3A | 0.2A |
Current Range | 0~10.5A | 0~3A | -------- | 0~5A | 0~3A | --------- | 0~2.5A | 0~3A | --------- |
Rated Power | 152.75W | 152.75W | 149.9W | ||||||
Ripple & Noise | 150mVp-p | 100mVp-p | -------- | 200mVp-p | 100mVp-p | ------- | 240mVp-p | 100mVp-p | --------- |
Voltage Adj. Range | CH1:12~14.5V | CH1:24~29V | CH1:48~58V | ||||||
Voltage Tolerance | ±2.0% | ±3.0% | -------- | ±1.0% | ±3.0% | -------- | ±1.0% | ±5.0% | --------- |
Line Regulation | ±1.0% | ±0.5% | -------- | ±1.0% | ±0.5% | -------- | ±1.0% | ±0.5% | --------- |
Load Regulation | ±1.0% | ±2.0% | -------- | ±1.0% | ±2.0% | -------- | ±1.0% | ±2.0% | --------- |
Setup, Rise Time | 1000ms, 90ms/230VAC 2000ms, 90ms/115VAC at full load | ||||||||
Hold Up Time | 24ms/230VAC 20ms/115VAC at full load | ||||||||
INPUT | |||||||||
Voltage Range | 88~264VAC 47~63Hz; 124~370VDC | ||||||||
AC Current | 2.5A/115VAC 1.5A/230VAC | ||||||||
Efficiency | 78% | 81% | 81% | ||||||
Inrush Current | Cold start 20A/115VAC 40A/230VAC | ||||||||
Leakage Current | <1mA /240VAC | ||||||||
PROTECTION | |||||||||
Over Load | CH1,CH2:105 ~ 135% CH3:0.51 ~ 0.9A rated output power | ||||||||
Protection type: AC Charging Mode: Hiccup mode, recovers automatically after fault condition is removed UPS Mode: Protected by internal fuse | |||||||||
Over Voltage | CH1:15.87~18.63V | CH1:31.74~37.26V | CH1:62.1~72.9V | ||||||
Protection type: Hiccup mode, recovers automatically after fault condition is removed | |||||||||
Battery Low | 10V±0.8V | 19.5V±1.5V | 39V±2V | ||||||
ENVIRONMENT | |||||||||
Working Temp. | -10~+60ºC (Refer to "Derating Curve") | ||||||||
Working Humidity | 20~90%RH non-condensing | ||||||||
Storage Temp., Humidity | -20~+85ºC,10~95%RH | ||||||||
Temp. Coefficient | ±0.03%/ ºC(0~50ºC )on CH1 output | ||||||||
Vibration | 10~500Hz,2G10min./1cycle,60min.each along X, Y,Z axes | ||||||||
SAFETY &EMC | |||||||||
Safety Standards | Design refer to UL60950-1, TUV EN60950-1 | ||||||||
Withstand Voltage | I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC | ||||||||
Isolation Resistance | I/P-O/P,I/P-FG,O/P-FG:100M Ohms/500VDC /25ºC /70%RH | ||||||||
EMC Emission | Compliance to EN55022(CISPR22) Class B, EN61000-3-2,-3 | ||||||||
EMC Immunity | Compliance to EN61000-4-2,3,4,5,6,8,11,EN55024,light industry level, criteria A | ||||||||
OTHERS | |||||||||
Dimension | 119*11*50mm(L*W*H) | ||||||||
Weight | 1Kg | ||||||||
Packing | 16pcs/16Kg/0.95CUFT | ||||||||
NOTE | |||||||||
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25ºC of ambient temperature. 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. 3. Tolerance: includes set up tolerance, line regulation and load regulation. 4. The power supply is considered a component which will be installed into final equipment. The final equipment must be re-confirmed that it still meets EMC directives. | |||||||||