Xt 160A 250A MCCB Lbs Breakers

Min.Order: 1
Product origin: Wenzhou, Zhejiang, China
Infringement complaint: complaintComplaint
US$ 11.5 ~ 330

Description
Product Description



MZ(S)Moulded case circuit breaker,AC690V,50/60HZ 

Rated current from 12.5A to 1000A 
CE Certificate approved 
2P,3P,4P all ok

MZ(S)Series Moulded case circuit breaker is mainly suitable for using in the electric Power system AC 50Hz, rated insulated voltage 690V (insulated voltage 400V in the Controlled circuit) and rated operating voltage up to 690V, used for distribution And overload, short circuit and underload protection of circuit and equipment, And also for the infrequent making and breaking circuit under normal conditions.

Detailed Photos

Product Parameters
Rated uninterrupted current(Iu)A160250250/320/400/630
Number of polesNO.3   4 3   4 3   4 
Rated operating voltage(Ue)(AC)50/60Hz V690690690
 DC V500500750
Rated impulse withstand voltageka888
Rated insulation voltageV8008001000
Frequency test voltage 1 minuteV300030003500
Rated ultimate short circuit breaking capacity(Icu) NSHLNSNSHLV
(AC)50/60Hz 220/230Vka658510012050857085100200200
(AC)50/60Hz 380/400V/415Vka365070853650365070120200
(AC)50/60Hz 440Vka304555752540304065100180
(AC)50/60Hz 500Vka25303650203025305085150
(AC)50/60Hz 690Vka67810582025407080
(DC) 250V 2P in serieska365070853650365070100150
(DC) 250V 3P in serieska4055851004055.....
(DC) 500V 2P in serieska......25365070100
(DC) 500V 3P in serieska365070853650.....
(DC) 750V 3P in serieska......1625365070
Rated short-circuit breaking capacity(Ics)            
(AC)50/60Hz 220/230V%Icu100%100%100%75%75%50%     
(AC)50/60Hz 380/400V/415V%Icu100%100%100%75%(70ka)75%50%(24ka)     
(AC)50/60Hz 440V%Icu100%100%100%75%75%50%     
(AC)50/60Hz 500V%Icu100%100%100%75%75%50%     
(AC)50/60Hz 690V%Icu100%100%100%75%75%50%     
Rated short-circuit breaking capacity(Icm)            
(AC)50/60Hz 220/230Vka143187220264       
(AC)50/60Hz 380/400V/415Vka75.6105154187       
(AC)50/60Hz 440Vka6391.5121165       
(AC)50/60Hz 500Vka52.56375.6105       
(AC)50/60Hz 690Vka9.211.913.617       
Opening time(415V)ms3333       
Use of times(415V) A          
Reference Standard IEC 60947-2          
Isolation .          
Release,Thermal-magnetic            
T is not Adjustable,M is not adjustable  TMF.          
T is not Adjustable,M is not adjustable  TMD.          
T adjustable,M adjustable (5..10*ln)TMA.          
T adjustable,M adjustable (3*ln)TMG.          
T adjustable,M adjustable (2.5…5*ln)TMG.          
ElectromagneticPR221DS.(MF up to In 12.5A)          
 PR221GP/PR221MP.          
 PR222DS.          
 PR223DS.          
 PR231/P.          
 PR232/P.          
 PR331/P.          
 PR332/P.          
Interchangeability .          
Type F-P          
Terminal TypeFixedF-FC Cu-FC CuAl-EF-ES-R          
 Plug-inF-FC Cu-FC CuAl-EF-ES-R          
 Out of style.          
On the DIN rail            
Mechanical lifeOperating cycles 25000         
 Operating cycles per hour 240         
Electrical lifeOperating cycles 8000         
 Operating cycles per hour 120         
Basic dimensions- fixed 3pole3poleW/L(mm)90         
  W/L(mm)120         
 4 poleD(mm)70         
  H(mm)130         
WeightFixed3/4 pole(kg)1.1/1.5         
 Plug-in3/4 pole(kg)1.5/1.9         
 Out of style3/4 pole(kg).         