Load a single set of system parameters | |
Rated voltage and frequency | AC three-phase four-wire 690V, 50Hz / 60Hz AC three-phase three-wire 400V, 50Hz / 60Hz |
Load rated power | Resistive load: 200 0kW, inductive load: 1939kvar, apparent power: 1800kVA (When the input voltage is below the rated voltage, load the actual power by Ohm's law descending) |
Maximum load power | 690V/ 400V, when 50Hz, resistive load: 4010 kW, inductive load: 2410kvar |
Load Binning | In 690V/400V, 60Hz calibration sub-file, sub-file as follows: Resistive Load: point 28 stalls, 1, 2, 2, 5, 10, 20, 20, 50, 100,200 × 19 (Unit: kW) Inductive load: min 21 files, 0 5, 1, 2, 2, 5, 10, 20, 20, 50, 100, 200 × 11. (Unit: kvar) Other voltage and frequency corresponding to the power of the power See table 5.6 |
Power Factor | 0.9 (0.1 ~ 1 adjustable) |
Load accuracy (per file) | ± 5% |
Load accuracy (whole) | ± 3% |
Display accuracy | 0.5 |
Control Power | External AC three-phase four-wire 380V/50Hz, 50kW |
Wiring | Load Power Input - copper (Manual Star - Delta Connection conversion) Control power input - terminal block |
Wiring port design | Allow sufficient space to ensure that users can easily access the load cables. External load penetrating openings in the cables after the cables have sufficient waterproof capability, and sufficient mechanical strength. |
Communication Interface | RS485, RS232 |
And machine methods | Computer software and machine |
Insulation class | Class F |
Protection class | IP56 (save state) |
Noise | 3 m away from the outlet is less than 9 0 db |
Work | Continuous work |
Cooling | Forced air, side air intake on the wind |
Chassis construction | Container package, with up to the top of the ladder, with inlet and outlet grilles and door protection |
Transport | There bearing hanging hole, in line with lifting and transport conditions. |
Chassis Size | Approximately 9000mm × 2 500 mm × 2 900mm (L × W × H) |
Weight | Approximately 20 000kg |
Work environment parameters | |
Workplace | Coastal areas, outdoor work |
Operating Temperature | - 25 ºC ~ + 6 0 ºC (lower limit of the instrument's temperature-10 ºC) |
Relative Humidity | ≤ 95% |
Altitude | ≤ 2500m |
Atmospheric pressure | 86 ~ 106kPa |