Supply voltage | 380~480Vac(-15%~+10%) |
Allowable voltage unbalance | < 3% |
Power supply frequency | 50/60Hz ±5% |
Displacement power factor | > 0.98 |
Harmonic interference Comply with EN61800-3 and EN12015 | |
Output voltage | 0-100% supply voltage |
Output frequency | 0-600Hz |
Overload performance | Light load application 110%, 1min; heavy load application 150%, 1min; allowable overload frequency 1mim/10min |
Maximum efficiency | ≥96%~99% |
Control mode | High-performance scalar, open-loop vector, closed-loop vector |
Starting torque | 150%, 3Hz; 150%, 3Hz; 200%, 0Hz |
Carrier frequency | 1.5-16kHz, carrier can be automatically adjusted according to the load |
AVR technology | Automatic regulation under bus voltage fluctuation to stabilize output voltage |
Frequency resolution | 0.01Hz |
Operation mode | Speed mode, torque mode, position mode |
Command channel | Panel, control terminal, communication |
Speed channel | Panel, digital quantity, analog quantity, communication, pulse, internal calculation |
Programmable digital input | 7 channels, maximum load current 100mA |
High-speed pulse input signal | 1 channel, 0-33kHz |
Analog input | 2 channels, 0-10V or 0 (4) -20mA |
Programmable digital output | 2 channels, maximum drive capacity 20mA |