Model | AW-CFP2166-2/4W | |||
Main Voltage | 220VAC 50HZ/60HZ | |||
Batteries | 2*12V/ 2.3Ah sealed lead acid gel, self-regulated | |||
Battery low-voltage protection | 21V | |||
Detectors connection allowed each zone | 20 detectors (except MCPs) | |||
Zone alarm current | 6mA minimum/ 27mA maximum | |||
Sounder output | 0.2A maximum | |||
Relay contacts rating | 1A @30VDC | |||
Loop output | 1 addressable horn strobe with transmitter each zone20 wireless devices for each addressable horn strobe | |||
EOL resistor for zone and sounder outputs | 6.8K ohm 1W | |||
Environmental | Class A temperature range: -5 to 40°C(23~104°F)Humidity: 5 to 95% RH, non-condensing | |||
Fuse for AC Power | 1 A/ 250V glass tube fuse slowblow5X20mm | |||
Fuse for DC Power | 1 A/ 250V glass tube fuse slowblow5X20mm | |||
Terminal blocks rating | All terminals rated for 12 to18 AWG(0.75to2.5mm²) |