IoT-Based multi channel branch circuits single phase or 3 phase Electricity Power Energy Meter
ADW210 multi loop energy meter adding AWT100-LoRa (down link:RS485 up link:LoRa and gateway AF-GSM300-HW868(down link LoRa up link
4G),then it can upload data by 4G to cloud platform supporting MQTT,http and other protocols.
Parameters of AEW210-D16-4S(LCD display,3 phase 4 circuit power metr with 12 CTs) | |||
Input Voltage | AC 3X220/380V | ||
Input Current | 600A | ||
Frequency | 45~65HZ | ||
Accuracy | 0.05Hz(frequency);0.5(voltage,current);1(active energy);2(reactive energy);±%(2-31st harmonics) | ||
Switching value | pulse output:Dry contact input,in-built power supply | ||
relay NO contact output;contact capacity:AC250V/3A DC30V/3A | |||
Communication | RS485,Modbus-RTU;baud rate 1200-38400 | ||
Basic functions | |||
3 phase voltage,current,zero sequence current and frequency measuring | |||
3 phase power,total power(active,reactive and apparent power),power factor and total power factor measuring | |||
voltage current phase angle,current voltage unbalance | |||
2-31st sub harmonic and total harmonic analysis(voltage and current) | |||
extreme value record of voltage,current and power in this month and last month | |||
max current,real current and power kwh max demand | |||
200 SOE,record DI and DO | |||
Support alarm output: over voltage,over current,phase loss,DI linkage and so on | |||
4 time zones and 14 time periods multi tariff setting | |||
4 quadrants energy,12 months multi tariff energy couting | |||
31 days 4 quadrant and multi tariff energy frozen | |||
accuracy:active energy class 1,reactive energy class 2 | |||
2DI2DO,1 active pulse output |
Extended function(optional) | |||
Switching value module(MK) | 12 DI | 12 DI, relay NO contact input and in-built power supply | |
4 DO | 4 DO, relay NO contact output;contact capacity:AC250V/3A DC30V/3A | ||
Communication | RJ45,modbus-rtu(communicate with ADW210 module | ||
power supply | RJ45,DC12V | ||
Temperature and leakage current module(MTL) | Temperature measuring | NTC input,range:-20ºC-100ºC | |
Leakage current measuring | residual current transformer :10-3000mA | ||
Accuracy | Temperature:±1ºC,leakage current:1 | ||
Communication | RJ45,modbus-rtu(communicate with ADW210 module | ||
power supply | RJ45,DC12V |
Type | Function |
AWT100-2G | 2G communication, RS485 interface, Wireless communication for auxiliary rs485 devices |
AWT100-4G | 4G communication, RS485 interface, Wireless communication for auxiliary rs485 devices |
AWT100-NB | NB-loT communication, RS485 interface, Wireless communication for auxiliary rs485 devices |
AWT100-LoRa | LoRa communication, RS485 interface, Wireless communication for auxiliary rs485 devices |
AWT100-LW | LoRaWAN communication, RS485 interface, Wireless communication for auxiliary rs485 devices |
AWT100-POW | AWT100 power module, power supply AC/DC220V |
Instrument type | Dimensions(mm) | |||
length | width | height | length(with terminal block) | |
ADW210 | 87.8 | 72 | 71.5 | 97.7 |
ADW210 module size | 87.8 | 36 | 71.5 | 105.5 |
CTs | Dimensions(mm) | Hole size(mm) | |||||
W | H | D | M | N | Φ1 | Φ2 | |
AKH-0.66/K-Φ16N | 31 | 50 | 36 | 27 | 42 | 16 | 17 |