Package | No. | Item | General Parameter | Remark |
1 | Combination Method | 16S | |
2 | Rated Capacity | Standard | 100Ah | Standard Discharge After Standard Charge (package) |
Minimum | 100Ah |
3 | Factory Voltage | 52.2-53.9V | Mean Operation Voltage |
4 | Voltage at End of Discharge | 42.5-45.5V | Discharge Cut-off Voltage |
5 | Charging Voltage | 57.6-58.4V | |
6 | Internal Impedance | ≤50mΩ | Internal Resistance measured at AC 1KHz After 50% Charge The Measure must uses the new batteries that within one week after shipment and cydesless than 5 times |
7 | Standard Charge | Constant Current 20A Constant Voltage see No.5 0.01CA cuff-off | Charge time : Approx 6H |
8 | Standard Discharge | Constant Current 20A Constant Voltage see No.4 | |
9 | Maximum Continuous Charge Current | 100A | |
10 | Maximum Continuous DisCharge Current | 100A | |
11 | Operation Temperature Ranage | Charge: 0~60°C | 60±25%R.H Bare Cell |
Discharge: -30~60°C |
12 | Storage Temperaature Range | Less Than 12Months: -10~35°C | 60±25%R.H at the shipment state |
Less Than 3Months: -10~45°C |
Less Than 7days: -20~60°C |
13 | Size | 442*460*177mm | Include case |
14 | Weight | 52KG | Include case |
15 | Volumetric Specific Energy | 142WH/L | Include case |
16 | Gravimetric Specific Energy | 98WH/KG | Include case |