Technical Parameter | Indicators | ||
Input | DC Voltage | Input Range | Direct Access: 0-100V, 0-500V, 0-1000V |
Input Resistance | ≥6kΩ/V | ||
DC Current | Input Range | Indirect Access: 0-2500A (External Shunt or Hall Sensor, the range can be set) | |
Shunt | 75mV | ||
Hall Sensor | 0-20mA, 0-5V | ||
Power Consumption | ≤1mW | ||
Overload | It can work at normal status at 1.2 times of full load, and can continued work 1 second at 2 times of full load. | ||
Accuracy Class | 0.5 Class | ||
Pulse Constant | Voltage and Current Specifications: 750V, 300A, Default Pulse Constant: 100imp/kWh | ||
Voltage and Current Specifications: 1000V, 300A, Default Pulse Constant: 100imp/kWh | |||
Voltage and Current Specifications: 1000V, 200A, Default Pulse Constant: 100imp/kWh | |||
Function | Measuring | Voltage, Current, Power | |
Calculate | Current Total Electricity, Current Positive Energy, Current Reverse Power | ||
Multiple Rate | Four Time Zones, Two Time Table, Fourteen Time Points, Four Multiple Rates. (PZ72L-DE Support Only) | ||
Historical Data Statistics | Last 12 Months of Historical Electricity (Multiple Rate Electricity). (PZ72L-DE Support Only) | ||
DI, DO | PZ72 has two digital outputs and two digital inputs, PZ96 has two digital outputs and four digital inputs. DI (Collect and Display Local Switch Status Information, Realize Remote Transmission by RS485), DO (Relay Output, Can Achieve "Remote Control" and Alarm Output) | ||
Display | LCD (The Backlight Delay Time Can Be Adjusted) / LED | ||
Communication | RS485, Half Duplex, Photoelectric Isolation, Modbus-RTU/DL/T645-07, Band: 1200/2400/4800/9600, Indrared: 1200 | ||
DI, DO | DI | Dry Contact Input, Meter Built-in Power Supply, Photoelectric Isolation | |
DO | Two Relay Outputs, Normally Open Contact, Capacity: 2A/30VDC 2A/250VDC | ||
Working Power | Voltage Range | 85-265VAC/DC, 50/60Hz, 20-60VDC/100-350VDC (Indicate When Placing An Order) | |
Power Consumption | ≤2W | ||
Insulation Resistance | ≥100MΩ | ||
Power Frequency | 3kV/1min (RMS) (Between The Power Supply Binding Post And The Signal Binding Post) | ||
Environment | Temperature | Working Temperature: -10ºC-+55ºC Storage Temperature: -25ºC-+70ºC | |
Humidity | ≤95% RH, No Condensation, No Corrosive Gases | ||
Altitude | ≤2000m |
Type | Display | Shape | Basic Function | Optional Function |
PZ72L-DE | LCD Display | 72 Square | DC: Voltage, Current, Power, Energy | /C: RS485 /V: 12V Power Output (Can't be selected with DI at the same time) /KC: RS485+2DO RS485+2DI2DO RS485+4DI2DO (PZ96) /KVC: RS485+2DO+12V Power Output /VC: RS485+12V Power Output /EC: RS485+0.001kWh The above functions can have the following two optional functions at the same time: /ZD: Auxiliary Power 20-60V /F: Multiple Rate |
PZ72-DE | LED Display | |||
PZ96L-DE | LCD Display | 96 Square | ||
PZ96-DE | LED Display |