EDR-120-24 24VDC 5A 120W AC/DC Single Output Power Supply SMPS

Min.Order: 1
Product origin: Wenzhou, Zhejiang, China
Infringement complaint: complaintComplaint
US$ 9 ~ 12

Description
 
MODELEDR-120-12EDR-120-24EDR-120-48







OUTPUT
DC VOLTAGE12V24V48V
RATED CURRENT10A5A2.5A
CURRENT RANGE0 ~ 10A0 ~ 5A0 ~ 2.5A
RATED POWER120W120W120W
RIPPLE & NOISE (max.) Note.2100mVp-p120mVp-p150mVp-p
VOLTAGE ADJ. RANGE12 ~ 14V24 ~ 28V48 ~ 55V
VOLTAGE TOLERANCE Note.3±2.0%±1.0%±1.0%
LINE REGULATION±0.5%±0.5%±0.5%
LOAD REGULATION±1.0%±1.0%±1.0%
SETUP, RISE TIME1200ms, 60ms/230VAC 2500ms, 60ms/115VAC at full load
HOLD UP TIME (Typ.)16ms/230VAC 10ms/115VAC at full load



INPUT
VOLTAGE RANGE Note.690 ~ 264VAC 127 ~ 370VDC[DC input operation possible by connecting AC/L(+), AC/N(-)]
FREQUENCY RANGE47 ~ 63Hz
EFFICIENCY (Typ.)85%87.5%88.5%
AC CURRENT (Typ.)2.25A/115VAC 1.3A/230VAC
INRUSH CURRENT (Typ.)20A/115VAC 35A/230VAC
LEAKAGE CURRENT<1mA / 240VAC



PROTECTION

OVERLOAD
105 ~ 130% rated output power
Protection type : Constant current limiting, recovers automatically after fault condition is removed

OVER VOLTAGE
14 ~ 17V29 ~ 33V56 ~ 65V
Protection type : Shut down o/p voltage, re-power on to recover
OVER TEMPERATUREShut down o/p voltage, re-power on to recover



ENVIRONMENT
WORKING TEMP.-20 ~ +60ºC (Refer to "Derating Curve")
WORKING HUMIDITY20 ~ 95% RH non-condensing
STORAGE TEMP., HUMIDITY-40 ~ +85ºC, 10 ~ 95% RH
TEMP. COEFFICIENT±0.03%/ºC (0 ~ 50ºC)
VIBRATIONComponent:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6

SAFETY & EMC
(Note 4)
SAFETY STANDARDSUL508, TUV EN62368-1, EAC TP TC 004, BSMI CNS14336-1 approved;(meet EN60204-1)
WITHSTAND VOLTAGEI/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
ISOLATION RESISTANCEI/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25ºC/ 70% RH
EMC EMISSIONCompliance to EN55032 (CISPR32) Class A, EN61000-3-2,-3, EAC TP TC 020, CNS13438 Class A
EMC IMMUNITYCompliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2 (EN50082-2), heavy industry level, criteria A, EAC TP TC 020

OTHERS
MTBF474.6K hrs min. MIL-HDBK-217F (25ºC)
DIMENSION40*125.2*113.5mm (W*H*D)
PACKING0.6Kg; 20pcs/13Kg/1.16CUFT
NOTEAll parameters NOT specially mentioned are measured at 230VAC input, rated load and 25ºC of ambient temperature.
Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
Tolerance : includes set up tolerance, line regulation and load regulation.
The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives.
lnstallation clearances : 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently with full power. ln case the adjacent device is a heat source, 15mm clearance is recommended.
Derating may be needed under low input voltage. Please check the derating curve for more details.
The ambient temperature derating of 3.5ºC/1000m with fanless models and of 5ºC/1000m with fan models for operating altitude higher than 2000m(6500ft}.

 
Product Tag:
Related categories:
Scroll to Top