Xinghai Pw-33-Y Ceramic 33Kv Pin Insulator for Power Transmission
Catalog No. | A1001 | A1002 | A1003 | A1004 | A1005 | A1006 | A1007 | ||
Fig | 1 | 1 | 2 | 3 | 4 | 5 | 6 | ||
Class Bs | P-11-Y | P-15-Y | P-20-Y | P-33-Y | Pw-11-Y | Pw-22-Y | Pw-33-Y | ||
Main Dimensions (mm) | H | 133 | 137 | 195 | 244 | 185 | 255 | 320 | |
h | 48 | 48 | 52.63 | 52.63 | 52.63 | 52.63 | 52.63 | ||
D | 140 | 152 | 230 | 279 | 170 | 205 | 240 | ||
d | 18.29 | 18.29 | 27.78 | 27.78 | 76 | 76 | 76 | ||
d2 | 27.78 | 27.78 | 27.78 | ||||||
R1 | 13 | 13 | 19 | 19 | 16 | 16 | 16 | ||
R2 | 9.5 | 12.7 | 14.3 | 13 | 16 | 16 | 16 | ||
Nominal voltage/kv | 11 | 15 | 22 | 33 | 15 | 22 | 33 | ||
Creepage Distance ( mm) | 240 | 298 | 432 | 630 | 432 | 673 | 851 | ||
Minimum Flashover Voltage | Power-frequency | Dry /KV | 75 | 80 | 100 | 135 | 100 | 125 | 140 |
Wet /KV | 45 | 55 | 60 | 85 | 65 | 95 | 110 | ||
50% Impulse | Positive/kv | 100 | 130 | 160 | 185 | 150 | 190 | 210 | |
Negative/kv | 110 | 175 | 205 | ||||||
Withstand Voltage | One minute power-frequency | Dry /KV | 65 | 70 | 90 | 110 | 90 | 110 | 125 |
Wet /KV | 40 | 50 | 55 | 75 | 60 | 90 | 100 | ||
Impulse/kv | 110 | 150 | 140 | 180 | 200 | ||||
Radio-Influence-Voltage Date | Test Voltage to Ground/kv | 15 | 15 | 22 | 30 | 22 | 30 | 44 | |
Maximum RIV at 1000kHz/uV | 8000 | 8000 | 12000 | 16000 | 12000 | 16000 | 25000 | ||
Powe-frequence-puncture Voltage (KV) | 135 | 135 | 145 | 185 | 150 | 200 | 210 | ||
Cantilever Failing Load(KN) | 11 | 11 | 11 | 13 | 11 | 11 | 11 | ||
Weight /kg | 1.8 | 11.5 | 5 | 10 | 13 |