6-36kv Expulsion Cutout Fuse, Porcelain Drop out Fuse

Min.Order: 2,000
Product origin: Wenzhou, Zhejiang, China
Infringement complaint: complaintComplaint
US$ 24

Description
*INSTRUCTION
Expulsion Fuse Cutout (Drop out fuse cutout) is used for outdoor medium voltage and high voltage alternative current system, which mainly protects transformer and distribution power line from short circuit and overload.
The fuse carrier drops out when the fuse link melted.
Standard type fuse cutout with solid link can function like overhead disconnect switch 200 amp.
Products are completely in accordance with IEC60282-2,ANSI C37.41,ANSI C37.42 standard.
 
*Our Strength
-More than 10 years of production experience;
-Sample order is available;
-Commercialization is available.
-Continuous improvement and perfection of products;
-High productivity, large spare parts inventory.

*Design Highlights
√Fuse carrier
 -Made of epoxy glass fiber lined with UV resistant coating and arc-extinguishing material, the fuse tube does not absorb moisture or deform.
 -The fuse carrier adopts single exhaust design (downward) with a solid cap which can prevent water intrusion and to avoid the threat of free gas to the circuit, unnecessary mechanical damage or short circuit.

√Contact
-The higher contact is made of pure conductive copper or highly elastic conductive copper alloy with silver plating;
-The lower contact is made of 60%~62% content brass with sliver plating.

√Terminals
-Both higher and lower terminals are made of 60%~ 62% content brasses with sliver or tin plating


√Porcelain & Polymer insulator body
-Porcelain insulator base: made of bird-proof ceramic, adopted advanced casting technology and using cement, which can prevent broken of porcelain body caused by thermal expansion and contraction.
-Silicone rubber insulator base: silicone rubber material has already passed 1,000 hours of salt spray test.


12-15KV Series Expulsion Fuse Cut Out
Electrical characteristicsSpecificationUnit
Voltage10~15KV
Current100/200/300A
Frequency50/60Hz
Power frequency withstand voltage to earth (1 min)42KV
Power frequency withstand voltage phase to phase (1 min)48KV
Impulse voltage to earth95KV
Impulse voltage phase to phase110KV
Breaking current8KA
Creepage distance:220mm
Spare parts  
Mounting bracketwith/without 
Arc shortening rodwith/without 
Arc distinguish chamberwith/without 
Fuse linkwithout 
Material  
Copper content for brassBrass (60~60%) 
Conductive parts materialCopper with silver plated/Copper with tin plate 
InsulatorPorcelain/Polymer 
Fuse tubeFiber glass 
Package  
Qty/package1pc/carton
Service conditions  
Environment maximum temperature40ºC
Pollution levelII 
Altitude≤1000Meter
StandardIEC60282-2 
   

15-27KV  Series Expulsion Fuse Cut Out
Electrical characteristicsSpecificationUnit
Voltage15~27KV
Current100/200/300A
Frequency50/60Hz
Power frequency withstand voltage to earth (1 min)45KV
Power frequency withstand voltage phase to phase (1 min)50KV
Impulse voltage to earth125KV
Impulse voltage phase to phase140KV
Breaking current8KA
Creepage distance:320mm
Spare parts  
Mounting bracketwith/without 
Arc shortening rodwith/without 
Arc distinguish chamberwith/without 
Fuse linkwithout 
Material  
Copper content for brassBrass (60~60%) 
Conductive parts materialCopper with silver plated/Copper with tin plate 
InsulatorPorcelain/Polymer 
Fuse tubeFiber glass 
Package  
Qty/package1pc/carton
Service conditions  
Environment maximum temperature40ºC
Pollution levelII 
Altitude≤1000Meter
StandardIEC60282-2 
   

24-27KV Series Expulsion Fuse Cut Out
Electrical characteristicsSpecificationUnit
Voltage24~27KV
Current100/200/300A
Frequency50/60Hz
Power frequency withstand voltage to earth (1 min)50KV
Power frequency withstand voltage phase to phase (1 min)60KV
Impulse voltage to earth150KV
Impulse voltage phase to phase160KV
Breaking current8KA
Creepage distance:520mm
Spare parts  
Mounting bracketwith/without 
Arc shortening rodwith/without 
Arc distinguish chamberwith/without 
Fuse linkwithout 
Material  
Copper content for brassBrass (60~60%) 
Conductive parts materialCopper with silver plated/Copper with tin plate 
InsulatorPorcelain/Polymer 
Fuse tubeFiber glass 
Package  
Qty/package1pc/carton
Service conditions  
Environment maximum temperature40ºC
Pollution levelII 
Altitude≤1000Meter
StandardIEC60282-2 
   

24-33KV Series Expulsion Fuse Cut Out
Electrical characteristicsSpecificationUnit
Voltage27~33KV
Current100/200/300A
Frequency50/60Hz
Power frequency withstand voltage to earth (1 min)70KV
Power frequency withstand voltage phase to phase (1 min)80KV
Impulse voltage to earth170KV
Impulse voltage phase to phase180KV
Breaking current6KA
Creepage distance:660mm
Spare parts  
Mounting bracketwith/without 
Arc shortening rodwith/without 
Arc distinguish chamberwith/without 
Fuse linkwithout 
Material  
Copper content for brassBrass (60~60%) 
Conductive parts materialCopper with silver plated/Copper with tin plate 
InsulatorPorcelain/Polymer 
Fuse tubeFiber glass 
Package  
Qty/package1pc/carton
Service conditions  
Environment maximum temperature40ºC
Pollution levelII 
Altitude≤1000Meter
StandardIEC60282-2 
   

33-36KV Series Expulsion Fuse Cut Out
Electrical characteristicsSpecificationUnit
Voltage33~36KV
Current100/200/300A
Frequency50/60Hz
Power frequency withstand voltage to earth (1 min)70KV
Power frequency withstand voltage phase to phase (1 min)80KV
Impulse voltage to earth170KV
Impulse voltage phase to phase180KV
Breaking current6KA
Creepage distance:720mm
Spare parts  
Mounting bracketwith/without 
Arc shortening rodwith/without 
Arc distinguish chamberwith/without 
Fuse linkwithout 
Material  
Copper content for brassBrass (60~60%) 
Conductive parts materialCopper with silver plated/Copper with tin plate 
InsulatorPorcelain/Polymer 
Fuse tubeFiber glass 
Package  
Qty/package1pc/carton
Service conditions  
Environment maximum temperature40ºC
Pollution levelII 
Altitude≤1000Meter
StandardIEC60282-2 
   

Produnction Line Display: