UPS power supplier Model | EX1K | EX1KL | EX2K | EX2KL | EX3K | EX3KL |
Capacity | 1000VA/800W | 2000VA/1600W | 3000VA/2400W |
Input | Voltage | (115~300) VAC |
Frequency | 46~54Hz/56~64Hz (Adjustable via LCD panel) |
Output | Voltage | 220/230/240 (1± 1%) VAC (Adjustable via LCD panel) |
Frequency | 50/60Hz (Adjustable via LCD panel) 50Hz AC Mode: Follow AC Mode(AC Range 46~54Hz); Battery Mode: 50Hz (1± 0.2%) 60Hz AC Mode: Follow AC Mode(AC Range56~64Hz); Battery Mode: 60Hz(1± 0.2%) |
Output Wave Form | Sine Wave |
Back-up Time | Full Load | ≥ 5′ | Depends on the capacity of the external battery bank | ≥ 9′ | Depends on the capacity of the external battery bank | ≥ 5′ | Depends on the capacity of the external battery bank |
Half Load | ≥ 14′ | ≥ 21′ | ≥ 15′ |
Battery Nominal DC Voltage | 36VDC | 96VDC |
Transfer Time | 0ms |
Overload Capacity | 110%~150% maintain 30s then turn to bypass output, over 150% maintain 300ms |
Communications | RS-232+Intelligent Slot |
Environment | Temperature | 0C~40C |
Humidity | 15%~90% |
Dimensions (W*D*H)mm | 145*400*220 | 192*460*340 |
Net Weight (Kg) | 14 | 7 | 34 | 13.5 | 34.5 | 14 |