High Voltage Indoor Vacuum Circuit Breaker Vcb Vs1-12 with High End Quality

Min.Order: 1
Product origin: Wenzhou, Zhejiang, China
Infringement complaint: complaintComplaint
US$ 535 ~ 650

Description

PRODUCT DETAILS:

12KV Vacuum Circuit Breakers (VS1)

VS1 series indoor high voltage AC vacuum circuit breakers are indoor switching equipment with rated voltage of 12kV. It can be used for the control and protection of electrical facilities in industry and mining, buildings and substations, as well as in places with frequent operation. The products have high reliability and stability.

The vacuum circuit breaker is equipped with low power consumption modular spring operating mechanism to meet the requirements of electric and manual operation. After the mechanism stored energy, the closing operation is completed after receiving the closing signal or pressing the closing button by hand; After the closing action is completed, after receiving the opening signal or press the opening button by hand to complete the opening operation.

 Ambient air temperature range: -5° C to 40 ° C, in addition, average temperature measured in 24 hours does not exceed 35° C.
 Altitude <=1000m.
 Daily average relative humidity should not exceed 95%. Daily average water vapor pressure should not exceed 2.2kpa;
 Monthly average relative humidity should not exceed 90%. Monthly average vapor pressure should not exceed 1.8kPa.
 Keep away from fire, explosion, serious pollution, chemical corrosion and violent vibration.

Vacuum interrupter
 Vacuum interrupter adopts the world's advanced manufacturing technology of miniaturized and high-performance interrupter;
 Contact is made of copper chromium alloy, with high vacuum degree;
 Cup style axial magnetic field (AMF) arc extinguishing, providing stable breaking performance;
 A single circuit breaker completes 274 times of rated short-circuit breaking E2;


Modular Mechanism
 Modular mechanism design, highly standardized structure;
 Mechanism is easy to assemble / disassemble and easy to maintain;
 High reliability with less number of parts
 Integrated charging handle, makes operation convenient and easy


Pot-type Pole
 Environment friendly insulating material, PA66 provides light weight, high dielectric performance;
 Recyclable and easy disposal after product life cycle;
 Cost effective and reliable;


Vacuum Circuit Breaker
 Fully meets the requirements of IEC and GB standards;
 Complete interlocking, prevent misoperation, and provide safety in operation;
 Modular design, shortened delivery time;
 Small opening rebound and excellent performance;


Model explanation
VS1 - Product code
12 - 12KV
T - Spring Mechanism; M - Permanent Magnetic Mechanism
630 - 630A

25 - 25kA
W - Withdrawable type; F - Fixed type
150 - 150mm pole distance; 210 - 210mm pole distance; 1000 - 1000mm/1m pole distance
P - Potted type; E - Encapsulted type

Spring Mechanism
ModelPole
Distance 
(mm)
Rated
Current 
(A)
Breaking
Short-Circuit 
Capacity (kA)
Installation 
method
NoteMechanism
VS1-12/T630-25KA-W150P15063025Withdrawable typePotted typeSpring
VS1-12/T1250-25KA-W150P150125025Withdrawable typePotted typeSpring
VS1-12/T1250-31.5KA-W150P150125031.5Withdrawable typePotted typeSpring
VS1-12/T630-25KA-F150P15063025Fixed typePotted typeSpring
VS1-12/T1250-25KA-F150P150125025Fixed typePotted typeSpring
VS1-12/T1250-31.5KA-F150P150125031.5Fixed typePotted typeSpring
VS1-12/T630-25KA-W150E15063025Withdrawable typeEncapsulated typeSpring
VS1-12/T1250-25KA-W150E150125025Withdrawable typeEncapsulated typeSpring
VS1-12/T1250-31.5KA-W150E150125031.5Withdrawable typeEncapsulated typeSpring
VS1-12/T1600-31.5KA-W150E150160031.5Withdrawable typeEncapsulated typeSpring
VS1-12/T630-25KA-F150E15063025Fixed typeEncapsulated typeSpring
VS1-12/T1250-25KA-F150E150125025Fixed typeEncapsulated typeSpring
VS1-12/T1250-31.5KA-F150E150125031.5Fixed typeEncapsulated typeSpring
VS1-12/T1600-31.5KA-F150E150160031.5Fixed typeEncapsulated typeSpring
VS1-12/T630-20KA-W210P21063020Withdrawable typePotted typeSpring
VS1-12/T630-25KA-W210P21063025Withdrawable typePotted typeSpring
VS1-12/T1250-25KA-W210P210125025Withdrawable typePotted typeSpring
VS1-12/T1250-31.5KA-W210P210125031.5Withdrawable typePotted typeSpring
VS1-12/T1600-31.5-W210P210160031.5Withdrawable typePotted typeSpring
VS1-12/T2000-31.5-W1000P1000200031.5Withdrawable typePotted typeSpring
VS1-12/T2000-40-W1000P1000200040Withdrawable typePotted typeSpring
VS1-12/T2500-31.5-W1000P1000250031.5Withdrawable typePotted typeSpring
VS1-12/T3150-31.5-W1000P1000315031.5Withdrawable typePotted typeSpring
VS1-12/T3150-40-W1000P1000315040Withdrawable typePotted typeSpring
VS1-12/T4000-31.5-W1000P1000400031.5Withdrawable typePotted typeSpring
VS1-12/T630-20KA-F210P21063020Fixed typePotted typeSpring
VS1-12/T630-25KA-F210P21063025Fixed typePotted typeSpring
VS1-12/T1250-25-F210P210125025Fixed typePotted typeSpring
VS1-12/T1250-31.5-F210P210125031.5Fixed typePotted typeSpring
VS1-12/T1600-31.5-F210P210160031.5Fixed typePotted typeSpring
VS1-12/T2000-31.5-F1000P1000200031.5Fixed typePotted typeSpring
VS1-12/T2000-40-F1000P1000200040Fixed typePotted typeSpring
VS1-12/T2500-31.5-F1000P1000250031.5Fixed typePotted typeSpring
VS1-12/T3150-31.5KA-F1000P1000315031.5Fixed typePotted typeSpring
VS1-12/T3150-40KA-F1000P1000315040Fixed typePotted typeSpring
VS1-12/T630-20KA-W210E21063020Withdrawable typeEncapsulated typeSpring
VS1-12/T630-25KA-W210E21063025Withdrawable typeEncapsulated typeSpring
VS1-12/T1250-25KA-W210E210125025Withdrawable typeEncapsulated typeSpring
VS1-12/T1250-31.5KA-W210E210125031.5Withdrawable typeEncapsulated typeSpring
VS1-12/T1600-31.5-W210E210160031.5Withdrawable typeEncapsulated typeSpring
VS1-12/T1600-31.5-W275E275160031.5Withdrawable typeEncapsulated typeSpring
VS1-12/T2000-31.5-W1000E1000200031.5Withdrawable typeEncapsulated typeSpring
VS1-12/T2000-40-W1000E1000200040Withdrawable typeEncapsulated typeSpring
VS1-12/T2500-31.5-W1000E1000250031.5Withdrawable typeEncapsulated typeSpring
VS1-12/T3150-31.5-W1000E1000315031.5Withdrawable typeEncapsulated typeSpring
VS1-12/T3150-40-W1000E1000315040Withdrawable typeEncapsulated typeSpring
VS1-12/T4000-31.5-W1000E1000400031.5Withdrawable typeEncapsulated typeSpring
VS1-12/T4000-40-W1000E1000400040Withdrawable typeEncapsulated typeSpring
VS1-12/T630-25KA-F210E21063025Fixed typeEncapsulated typeSpring
VS1-12/T1250-25-F210E210125025Fixed typeEncapsulated typeSpring
VS1-12/T1250-31.5-F210E210125031.5Fixed typeEncapsulated typeSpring
VS1-12/T1600-31.5-F210E210160031.5Fixed typeEncapsulated typeSpring
VS1-12/T1600-31.5-F275E275160031.5Fixed typeEncapsulated typeSpring
VS1-12/T2000-31.5-F1000E1000200031.5Fixed typeEncapsulated typeSpring
VS1-12/T2000-40-F1000E1000200040Fixed typeEncapsulated typeSpring
VS1-12/T2500-31.5-F1000E1000250031.5Fixed typeEncapsulated typeSpring
VS1-12/T3150-31.5KA-F1000E1000315031.5Fixed typeEncapsulated typeSpring
VS1-12/T3150-40KA-F1000E1000315040Fixed typeEncapsulated typeSpring
VS1-12/T4000A-31.5KA-F1000E1000400031.5Fixed typeEncapsulated typeSpring
VS1-12/T4000A-40KA-F1000E1000400040Fixed typeEncapsulated typeSpring


Main Technical Specification
ItemUnitData
Rated voltagekV12
Rated frequencyHz50
Rated insulation level 1 min power frequency withstand voltage pole to earthkV42
Rated insulation level 1 min power frequency withstand voltage phasekV48
Rated insulation level lightning impulse withstand voltage pole to earthkV75
Rated insulation level lightning impulse withstand voltage phasekV85
Power frequency withstand voltage of secondary circuitV2000
Rated currentA630,1250, 1600, 2000, 2500, 3150, 4000, 5000
Rated short-circuit breaking currentkA20, 25, 31.5, 40, 50
Rated short-time withstand currentkA20, 25, 31.5, 40, 50
Rated short circuit durations4
Rated peak withstand currentkA50, 63, 80, 100, 125
Rated short-circuit making currentkA50, 63, 80, 100, 125
Rated short circuit current breaking times (class E2)times30
Rated single/back to back capacitor bank breaking currentA630/400,  800/400
Clearance between open contactsmm11±1
Contact strokemm3~4
Allowable wear thickness of contactmm3
Average opening speedm/s0.9~1.4
Average closing speedm/s0.5~1.0
Contact closing bounce timems≤2
Different phases of contact closing and openingms≤2
Rebound amplitude of opening contactmm≤2
Opening time (rated voltage)ms20~50
Closing time (rated voltage)ms30~70
Mechanical life (M2)ms10,000(20,000)
Rated operating voltageVAC110/220  DC110/220
Rated operation sequence O-0-CO-180s-CO