Rpm60m Power Meter Multi Meter Network Analyzer

Min.Order: 1
Product origin: Foshan, Guangdong, China
Infringement complaint: complaintComplaint
US$ 93 ~ 232

Description

Product Description


True RMS measurements (512 samples/cycle)
For single-phase, two-phase, three-phase system
Measurements:VL-L, VL-N, I, In, Cos , Pf, Hz, W, ∑W, Va, ∑Va, Var, ∑Var, import Kwh, export Kwh import Kvarh,
  export Kvarh, V-THD, I-THD,1-63th harmonic , system running hours, % voltage unbalance, % current unbalance,
  % system load, total frequency
3 voltage and 4 current input (Measure or calculate the neutral current)
Voltage Input: 0-690Vac, Current input: 1 or 5A CT selective
% system load and system running hours
Detects CT wiring errors
Maximum, minimum and demand for U, I, P, Q, S in hours, days, months
Real time clock with integrated backup rechargeable battery
4 quadrants energy measurement and  monthly energy calculation
2 pulse output and RS485 communication: Modbus RTU
Alarm event log
Built in 64Mbit flash memory for datalog
Data recorded in standard excel file formats for further En50160 analysis
Comply BEC2018 in clause7.7.1-7.7.3 store data:
  [Voltage(L-L, L-N), Current(3P and neutral), total power factor, total energy consumption(Kwh),maximum demand(kVA),
  total harmonic distortion for 3phase voltage and current] at least 3years in interval of 15 minutes
English, Chinese (traditional & simplied)
Moduel function options (only one can be selected)
   - 7 digital input +2 relay output(remote or alarm)(Standard)
   - 7 digital input +2 analog output(4-20mA) for V1,V2,V3,V12,V23,V31,I1,I2,I3 (option)
   - Ethernet (Modbus TCP), Web server+2 digital input +2 relay output(remote or alarm) (option)
   - LoRa wireless (Private protocol)+2 digital input+2 relay output (remote or alarm)(option)
   - RS-485 interface (Modbus RTU)+2 digital input+2 relay output (remote or alarm)(option)
   - WIFI wireless +2 digital input +2 relay output(remote or alarm) (option)

Product Parameters

Auxiliary Supply
Operating voltage (Un)85···265 VAC 50/60Hz 10W / 100-285VDC/24-48VDC(depend on order)
Power consumption4VA max
Measurement input
Voltage inputs for direct connection:Phase-neutral(L-N): max 400V RMS CAT III
Input impedance(for direct voltage inputs):>4MΩ
CT inputs:max 5.5A RMS
CT inputs overload capacity:max 10A
CT inputs Self-consumption :< 0.2VA
Accuracy
Three phase voltage:± 0.2%
Currents:± 0.2%
Powers:± 0.5%
Powers factor:± 0.5%
Frequency:± 0.02%
Harmonics:± 1%
Active energy:Class 0.5S
Reactive energy:Class 0.5S
Insulation
Insulation voltage
3kV for 1 min., 50Hz
Display
Display type
3.2inch 240x160 pix LCD
I/O
Digital inputs:
Active dry contact
Digital outputs:
2 Relay N/O 220VAC 5A
Analog outputs:
4-20mADC / max load 500Ω
Pulse output:
24-30VDC Max.50mA, Min. 50msec pulse width
Memory 
Recording memory:
64Mbit flash memory for Data log(USB port for download)
Communication
USB portfor download datalog
Ethernet port:
Auto MDIX Rj45 10/100 Base Ethernet
RS-485 port:
1 optoisolated, 4800-57600
Protocols:
HTTP, HTTPS, Modbus RTU/TCP
Environmental conditions
Opterating temperature:
-10···+55°C
Storage temperature:
-25···+75°C
Relative humidity:
95% max without condensing
Altitude:
max 2000m AMSL
Installation & use:
Internal
Mechanical characteristics
Mounting:
Panel mount 96x96mm(The panel cut-size 92*92mm)
Size:
Front(WXH)96x96mm, Rear (HxD) 90x70mm
Degree of protection:
IP40(optional IP54) on front, IP20 housing and terminals
Weight:
400g
Standard compliance
reference standard:
IEC61010-1; IEC61557-1;IEC61557-12; IEC61326-1;IEC62053-21;
IEC62053-22; IEC62053-31; IEC60068-2-1; IEC60068-2-30;
IEC60364-5-52; IEC61000-3-2; IEC61000-3-3; IEC61000-4-2;
IEC61000-4-3; IEC61000-4-4; IEC61000-4-5; IEC61000-4-6;
IEC61000-4-8; IEC61000-4-11; IEC61000-4-30