Function | iron core grounding current test, AC leakage current, current, frequency, waveform online analyze test |
Power | DC7.4V large capacity rechargeable lithium battery, USB interface, fully charged continuous work 8 hours |
Rated current | About 180mA max |
Display mode | 3.5 inches true color LCD display |
Meter dimension | Host: 207mm(L) x 101mm(W) x 45mm(D) |
Current Clamp: 153mm x 290mm x 41mm |
Clamp mouth | 88mm x 88mm |
Measurement Range | Current: 0.0mA~400.0A(50Hz/60Hz) |
Frequency: 10Hz~1000Hz |
Resolution | AC 0.1mA |
Accuracy | 0.0mA~100.0mA ±2%±3dgt |
100mA~2000mA ±1%±3dgt |
2.00A~20.00A ±1%±3dgt |
20.0A~400.0A ±1%±3dgt |
Detect rate | about 2s each time |
Data hold | press "HOLD" key to hold datas, "HD" symbol display |
Data reserve | 200 groups |
LCD brightness | press "UP/DOWN" key to adjust LCD background brightness |
Alarm set | alarm critical value set range: 10mA~30.00A |
Alarm indicate | when the test value exceeds alarm critical value, indicator flash, buzzer buzzling |
Battery voltage | when the battery voltage is less than 6.5V, battery voltage "low symbol" displays, prompt charge for the battery |
Auto shutdown | After start up 30mins, meter will automatically shutdown to reduce battery consumption |
Meter weight | Host: 370g(including battery) |
Current clamp: 720g |
Total weight: 1.6kg |
Recharge interface | USB interface |
Current clamp wire length | 2.7m |
Working temperature/humidity | -10ºC~40ºC, 80%RH and below |
Save temperature/humidity | -10ºC~60ºC, 70%RH and below |
Electric field interference | outer electric field 100A , approach to 10mm about 20mA |
Withstand voltage | meter circuit and outer house withstand 1000V/50Hz, sine wave AC voltage withstand 1min |
Insulation | meter circuit and protective house ≥100MΩ |
Structure | Dual insulation, with insulated shockproof protective set |
Meet | IEC61010-1 CAT III 600V, IEC-61010-031, IEC-61326, pollution grade 2 |