Transformer iron core grounding current tester is specially designed for on-site testing of transformer iron core's grounding current, leakage current, frequency, waveform. It is composed of host, current clamp, data software, communication wires, etc. 

Technical Parameters
Functioniron core grounding current test, AC leakage current, current, frequency, waveform online analyze test
PowerDC7.4V large capacity rechargeable lithium battery, USB interface, fully charged continuous work 8 hours
Rated currentAbout 180mA max
Display mode3.5 inches true color LCD display
Meter dimensionHost: 207mm(L) x 101mm(W) x 45mm(D)
Current Clamp: 153mm x 290mm x 41mm
Clamp mouth88mm x 88mm
Measurement RangeCurrent: 0.0mA~400.0A(50Hz/60Hz)
Frequency: 10Hz~1000Hz
ResolutionAC 0.1mA
Accuracy0.0mA~100.0mA       ±2%±3dgt
100mA~2000mA       ±1%±3dgt
2.00A~20.00A           ±1%±3dgt
20.0A~400.0A           ±1%±3dgt
Detect rateabout 2s each time
Data holdpress "HOLD" key to hold datas, "HD" symbol display
Data reserve200 groups
LCD brightnesspress "UP/DOWN" key to adjust LCD background brightness
Alarm setalarm critical value set range: 10mA~30.00A
Alarm indicatewhen the test value exceeds alarm critical value, indicator flash, buzzer buzzling
Battery voltagewhen the battery voltage is less than 6.5V, battery voltage "low symbol" displays, prompt charge for the battery
Auto shutdownAfter start up 30mins, meter will automatically shutdown to reduce battery consumption
Meter weightHost: 370g(including battery)
Current clamp: 720g
Total weight: 1.6kg
Recharge interfaceUSB interface
Current clamp wire length2.7m
Working temperature/humidity-10ºC~40ºC, 80%RH and below
Save temperature/humidity-10ºC~60ºC, 70%RH and below
Electric field interferenceouter electric field 100A , approach to 10mm about 20mA
Withstand voltagemeter circuit and outer house withstand 1000V/50Hz, sine wave AC voltage withstand 1min
Insulationmeter circuit and protective house ≥100MΩ
StructureDual insulation, with insulated shockproof protective set
MeetIEC61010-1  CAT  III 600V,  IEC-61010-031, IEC-61326, pollution grade 2

Working Conditions
Affect factorsBasic conditionsWorking conditions
environment temperature23ºC±1ºC-10ºC~40ºC
environment humidity40%~60%<80%
signal frequency50Hz ± 1Hz10Hz~1000Hz
meter working voltage7.4V ± 0.5V7.4V ± 1V
waveform current amplitude/10mA~400A
outer electric field, magnetic fieldshould avoid
Tested wires positionthe tested wire approach to the center of clamp mouth

Company Profile:
Wuhan Hezhong Electric Equipment Manufacture Co., Ltd is a high-tech enterprise professionally engaged in R & D, manufacture and marketing of power testing products, instruments, power industry automation systems for 20 years.We export completed set to Korea, Singapore, Vietnam, India, Ecuador, Paraguay, Pakistan, Philippines, Russia, Italy, Austria, Portugal, Chile such as PD test system, impulse voltage generator, temperature rising test system, transformer comprehensive test system, cable fault detect system and varies of instruments for transformer, circuit breaker, switchgear, lightning arrestor, insulator, cable, battery, SF6 gas and so on.