Circuit Breaker Specification:
Type | Rated current (A) | Number of Poles | Rated insulation voltage(V) | Rated operating voltage(V) | Arcing-Over Distance(mm) | Ultimated short Circuit Breaking Capacity(KA) | Service Short Circuit Breaking Capacity(KA) | Operation performance(time) | |
ON | OFF | ||||||||
RM1-100D | 12.5,16,20,25, 32,40, 50,63, 80, 100 | 3P/4P | 950V | 690V | 0 | 18 | 18 | 1500 | 8500 |
RM1-100N | 25 | 25 | |||||||
RM1-100H | 70 | 70 | |||||||
RM1-160D | 100,125,160,180, 200 | 3P/4P | 950V | 690V | 0 | 25 | 25 | 1500 | 7000 |
RM1-160N | 36 | 35 | |||||||
RM1-160H | 70 | 70 | |||||||
RM1-250D | 160,180,200,225, 250 | 3P/4P | 950V | 690V | 0 | 25 | 25 | 1000 | 4000 |
RM1-250N | 36 | 36 | |||||||
RM1-250H | 70 | 70 | |||||||
RM1-400D | 200,225,250,300, 215, 400 | 3P/4P | 950V | 690V | 0 | 35 | 35 | 1000 | 4000 |
RM1-400N | 45 | 45 | |||||||
RM1-400H | 70 | 70 | |||||||
RM1-630D | 400, 500, 630 | 3P/4P | 950V | 690V | 0 | 75 | 75 |
Circuit Breaker Tripping Characteristics:
Rated current of release (A) | Thermodynamic release | (ambient temp+40) | Operational current of magneticrelease (A) | ||
1.05In(cold state) inoperative time (h)
| 1.I3n 0h(eat state)inoperative time(h) | ||||
In<63 | ≥1 | <1 | 10In±20% | ||
63<In<100 | ≥2 | <2 | 10In±20% | ||
100<In<630 | ≥2 | <2 | 5-10In±20% | ||
Rated current of release (A) | Thermodynamic release(ambient temp+40ºC) | ||||
1.0In (cold state) | 1.20In (heat state) | 1.50In (heat state) | 7.2In (heat state) | Operational current of magnetic release (A) | |
12.5<In<400 | ≥2h | <2h | <4min | 2S<Tp<10s | 12In±20% |