Company Info
Realm, as a global leader in heat pump industry, has advanced and innovative technologies such as EVI air jet enthalpy increasing and heat saving technology, exquisite technology with large windward area, three-stage defrosting technology, anti-ice storage technology , and temperature compensation. These technologies fully address the problems of reliable operation and super heating of heat pump under low temperature in winter. This is very energy efficient.
Guangzhou Realm energy saving equipment Co., Ltd. has been providing high-quality products and considerate services for decades with its safe and reliable design, the pursuit of ingenuity and quality, and the integration of DC inverter technology. The company is committed to providing global consumers with safe, healthy, comfortable, and intelligent ideal life.
Product Info
Parameters
Model No. | RMAW-05ZR3-V |
Transport Package | Plywood RMRB Boxes |
Trademark | RMRB |
power Supply | 220-240V |
Specifications | 995*470*1385MM |
Origin | China |
Production Capacity | 5oooosets per year |
RMRB DC INVERTER HEAT PUMP WITH WIFI | ||||||||
MODEL MODOBLACK | RMAW-03ZR1-V | RMAW-04ZR1-V | RMAW-05ZR3-V | RMAW-06ZR3-V | RMAW-08ZR3-V | RMAW-10ZR3-V | ||
MODEL SPLIT | RMAW-03FR1-V | RMAW-04FR1-V | RMAW-05FR3-V | RMAW-06FR3-V | / | / | ||
HP | 3HP | 4HP | 5HP | 6HP | 8HP | 10HP | ||
power supply | 220-240V,50Hz,1Ph | 220-240V,50Hz,1Ph(380-415V,50Hz,3Ph) | ||||||
Heating 1 | Capacity(kw) | 8.7 | 11.2 | 17.2 | 18.9 | 22.0 | 33.7 | |
Rate input(kw) | 2.0 | 2.8 | 4.2 | 4.4 | 5.5 | 8.2 | ||
Cop | 4.3 | 4.0 | 4.1 | 4.3 | 4.0 | 4.1 | ||
Heating 2 | Capacity(kw) | 8.2 | 10.6 | 16.1 | 17.8 | 21.5 | 31.6 | |
Rate input(kw) | 2.5 | 3.3 | 5.0 | 5.4 | 6.6 | 9.8 | ||
Cop | 3.3 | 3.2 | 3.2 | 3.3 | 3.3 | 3.2 | ||
Heating 3 | Capacity(kw) | 7.8 | 10.0 | 15.1 | 16.7 | 19.6 | 29.6 | |
Rate input(kw) | 3.0 | 3.9 | 6.0 | 6.6 | 7.7 | 11.7 | ||
Cop | 2.6 | 2.6 | 2.5 | 2.5 | 2.6 | 2.5 | ||
Cooling 1 | Capacity(kw) | 7.9 | 10.2 | 15.1 | 16.2 | 20.0 | 29.6 | |
Rate input(kw) | 2.4 | 3.4 | 4.4 | 4.7 | 6.6 | 8.7 | ||
EER | 3.3 | 3.1 | 3.2 | 3.4 | 3.1 | 3.2 | ||
Cooling 2 | Capacity(kw) | 6.7 | 8.5 | 12.5 | 13.8 | 15.6 | 24.5 | |
Rate input(kw) | 2.4 | 2.9 | 4.7 | 5.3 | 5.9 | 9.2 | ||
EER | 2.8 | 2.9 | 2.5 | 2.8 | 2.9 | 2.5 | ||
Seasonal Space Heating | LWT at 35ºC | A+++ | A+++ | A+++ | A+++ | A+++ | A+++ | |
energy efficiency class | LWT at 55ºC | A++ | A++ | A++ | A++ | A++ | A++ | |
Refrigerant | Type(GWP) | R32 / R410A | ||||||
Charged volume(kg) | 1.80 | 2.10 | 3.00 | 3.10 | 3.60 | 3.90 | ||
Sound Power level | DB(A) | 57 | 59 | 60 | 61 | 62 | 62 | |
Net Dimension(W*H*D) | MM | 995*1000*420 | 995*1385*470 | 1200*1450*570 | 1195*1385*570 | |||
Packing Dimension(W*H*D) | MM | 1060*1140*510 | 1060*1530*510 | 1265*1515*625 | 1265*1515*625 | |||
Net/Gross Weight | KG | 110/115 | 125/142 | 150/168 | 155/168 | 160/173 | 195/210 | |
Water pump | Max Pump head(M) | 8 | 8 | 8 | 8 | \ | \ | |
Water piping connection | MM | DN25 | DN32 | |||||
Ambient temperature range | Cooling | -5ºC to 46ºC | ||||||
Heating | -25ºC to 35ºC | |||||||
DHW | -25ºC to 43ºC | |||||||
LWT temperature range | Cooling | 25ºC to 65ºC | ||||||
Heating | 5ºC to 25ºC | |||||||
DHW | 30ºC to 60ºC | |||||||
Electric heater | KW | 3 | 3 | 3 | 3 | 3 | 3 | |
Split Outdoor unit | ||||||||
Net Dimension(W*H*D) | mm | 1050*1000*470 | 1050*1385*410 | / | / | |||
Packing Dimension(W*H*D) | mm | 1120*1122*520 | 1120*1532*480 | / | / | |||
Split Indoor unit | ||||||||
Net Dimension(W*H*D) | mm | 580*750*300 | 580*750*300 | / | / | |||
Packing Dimension(W*H*D) | mm | 650*828*382 | 650*828*382 | / | / | |||
Monoblock | 20GP/40GP/40HQ | set | 42/87/110 | 31/65/82 | 31/65/82 | 31/65/82 | 21/45/56 | 21/45/56 |
Split | 20GP/40GP/40HQ | set | 27/57/72 | 27/57/72 | 24/49/62 | 24/49/62 | / | / |
EXW (UNIT)Price for Monoblock | USD | US$1,500.00 | US$1,850.00 | US$2,150.00 | US$2,300.00 | US$2,550.00 | US$2,770.00 | |
EXW (UNIT)Price for Split | USD | US$1,650.00 | US$2,000.00 | US$2,300.00 | US$2,450.00 | US$2,700.00 | US$2,920.00 | |
Notes: | ||||||||
Heating 1 - Outdoor temperature: 7ºC DB/6ºC WB; entering water temperature: 30ºC; leaving water temperature: 35ºC . | ||||||||
Heating 2 - Outdoor temperature: 7ºC DB/6ºC WB; entering water temperature: 40ºC; leaving water temperature: 45ºC . | ||||||||
Heating 3 - Outdoor temperature: 7ºC DB/6ºC WB; entering water temperature: 47ºC; leaving water temperature: 55ºC . | ||||||||
Cooling 1 - Outdoor temperature: 35ºC; entering water temperature: 23ºC; leaving water temperature: 18ºC. | ||||||||
Cooling 2 - Outdoor temperature: 35ºC; entering water temperature: 12ºC; leaving water temperature: 7ºC. | ||||||||
* Seasonal space heating energy effiiciency class is tested in average climate general conditions. | ||||||||
Relevant EU standards and legislation: EN14511; EN14825; EN50564; EN12102; (EU)No 813/2013; QJ 2014/C 207/02:2014. |
Key Components
Certifications