1 Pole 125A Circuit Breaker for Overload Circuit Protection High Breaking Capacity MCCB

Min.Order: 100
Product origin: Wenzhou, Zhejiang, China
Infringement complaint: complaintComplaint
US$ 20

Description
 
Product Description
Application
1.CJMM1 series moulded case circuit breaker(hereinafter referred to as circuit breaker) is pplicable for AC 50/60HZ power distribution network 
circuit with rated insulation voltage of 800V, rated operation voltage of 690V and rated operation current from 10A to 630A, it's used to distribute power and prevent circuit and power supply equipment from damage due to overload, short circuit, under voltage and other faults, it's also used for infrequent start of motor as well as overload, short circuit and under voltage protection 

2.This circuit breaker owns advantages of small volume, high breaking capacity, short arcing (or noarcing)etc, it can be equipped with accessories like alarm contact, shunt release, auxiliary contact etc, it's an ideal product for user.

3.The residual current circuit breaker can either be vertically installed (vertical installation) or be horizontally installed (horizontal installation) 
The product is in accordance with the standards of IEC60947-2 and Gb140482

Classification
1.By breaking capacity: a standard type(type S) b higher breaking capacity type(type H)
2.By connection mode: a front board connection, b back board connection, c plugin type
3.By operation mode: a direct handle operation, b rotation handle operation,c electrical operation
4.By number of poles: 1P,2P, 3P, 4P 
5.By accessory: alarm contact, auxiliary contact, shunt release, under voltage release.


Normal Service Condition
1.The altitude of the installation site shall not exceed 2000m
2.Ambient air temperature
   a.The ambient air temperature shall not exceed +40ºC
   b.The average value shall not exceed +35ºC with in 24 hours
   c.The ambient air temperature shall not be less than-5ºC
3.Atmosphere condition
   a.There lative humidity of atmosp here shall not exceed 50% at highest temperature of +40ºC,and it can be higher atalower temperature,when theaver agelowest temperature in the wettest month doesn't exceed 25ºC can be 90%,conden sationon product surfacedue to temperature change must be takenin to account.
4.The pollution level is class 3

Table1
Accessory nameElectronic releaseCompound release
Auxiliary contact,under voltage release,alam contact287378
Two auxiliary contact sets,alarm contact268368
Shunt release, alarm contact, auxiliary contact238348
Under voltage release,alarm contact248338
Auxiliary contact alarm contact228328
Shunt release alarm contact218318
Auxiliary contact under-voltage release270370
Two auxiliary contact sets260360
Shunt release under-voltage release250350
Shunt release auxiliary contact240340
Under-voltage release230330
Auxiliary contact220320
Shunt release210310
Alarm contact208308
No accessory200300
 
Main Technical Parameter

1.Rated value of circuit breakers

ModelImax(A)Specifications(A)Rated Operation Voltage(V)Rated Insulation Voltage(V)Icu(kA)Ics(kA)Number of Poles (P)Arcing Distance(mm)
CJMM1-63S636,10,16,20
25,32,40,
50,63
40050010*5*3≤50
CJMM1-63H6340050015*10*3,4
CJMM1-100S10016,20,25,32
40,50,63,
80,100
69080035/1522/53≤50
CJMM1-100H10040080050352,3,4
CJMM1-225S225100,125,
160,180,
200,225
69080035/1525/53≤50
CJMM1-225H22540080050352,3,4
CJMM1-400S400225,250,
315,350,
400
69080050/1535/83,4≤100
CJMM1-400H40040080065353
CJMM1-630S630400,500,
630
69080050/1535/83,4≤100
CJMM1-630H63040080065453
Note: When the test parameters for the 400V, 6A without heating release

2.Inverse time breaking operation characteristic when each pole of overcurrent release for power distribution is powered on at the same time
Item of test Current (I/In)Test time areaInitial state
Non-tripping current 1.05In2h(n>63A),1h(n<63A)Cold state
Tripping current 1.3In2h(n>63A),1h(n<63A)Proceed immediately after No.1 test

3.Inverse time breaking operation characteristic when each pole of overcurrent release for motor protection is powered on at the same time.
Setting Current Conventional time Initial StateNote
1.0In>2hCold State 
1.2In≤2hProceeded immediately after the No.1 test 
1.5In≤4minCold State10≤In≤225
≤8minCold State225≤In≤630
7.2In4s≤T≤10sCold State10≤In≤225
6s≤T≤20sCold State225≤In≤630

4.The instantaneous operation characteristic of circuit breaker for power distribution shall be set as 10in+20%, and the one of circuit breaker formotor protection shall be set as12ln±20%
 