ATG wireless monitor console probe fuel tank gauge system
What are Tank Gauge System used for?
Gas station fuel tank gauge system are used for monitoring fuel level, water level and temperature inside fuel storage tanks. It is widely used at gas station and skid-mounted fueling site. It also can be used at chemical factory, pharmacy industry and waste water tanks.
The tank gauge smart console is a powerful product developed and produced by Windbell. Together with SP300 series magnetostrictive liquid level meter constitute the complete automatic tank gauge system.
The smart console is the display terminal of the automatic tank gauge system and can detect 1 to 12 tanks at the same time. It can monitor fuel level, water level, temperature, product volume, water volume, empty volume, all kinds of alarms, inventory and delivery information in real time.
International graphic touch screen and user-friendly icon, makes it is easy for new user.
SP300 Magnetostrictive sensor is mainly composed of probe head, temperature sensors, protection steel pipe, magnetostrictive waveguide wire and floaters with magnet inside. Insert probe into underground tank, floaters float on the liquid surface, and slides up and down on rod according to the changes of liquid level. Processing measured data of product level, water level, density values (option), and average temperature of five-points, then transmit these data to smart console by digital communication port.
SS200B Console | |
Power | 90 ~ 264VAC/127 ~370VDC |
Working temperature | -20 to 60ºC |
Installation location | Safety zone |
Display | WB-SS200-A: 8-inch color touch screen WB-SS200-B: 12-inch color touch screen |
Ex-proof grade | [EX ia Ga] IIB |
Safety barrier | -GSB05/GSB06/GSB-CL06 |
Relay output | 2 groups. Node capacity AC250V/3A. DC30V/3A |
External extension anti-overfill valve console | WB-DFV100-06A |
External extension submersible pump console | SS160-EM02 |
Output voltage | DC 12V |
Monitor probes | Up to 32 |
Leak sensor | Up to 64 |
SMS module | Optional |
GPRS module | Optional |
Built-in printer | Optional |
WIFI function | Optional |
External sound-light alarm | Optional |
External printer | Support |
Running/Alarm indicator | Yes |
Inventory and delivery management | Yes |
Density and mass measurement | Yes |
RS485 port | 1 |
RS232 port | 2 |
USB port | 1 |
Ethernet port | 1, 100M |
Buzzer alarm | Yes |
Tank table | Yes, simulate/input/import/export |
Reports | Inventory, delivery, shift, alarm, leak detection test, system log, SMS for optional |
PC remote software | PCR200 |
Anti-theft function | Yes |
Dimension (L*W*H) | 360*280*110mm |
Weight | 8kg |
SP300 Magnetostrictive Sensor | |
Power supply | DC12V |
Precision | ±0.5mm |
Repeatability | ±0.1mm |
Resolution of product level | 0.0069mm |
Resolution of temperature | 0.0078ºC |
Resolution of water level | 0.0069mm |
Temperature range | -40 to 85ºC(-40 to 185ºF) |
Points of temperature measured | 5 |
Maximum communication distance | 1200m |
Communication | RS485 |
Intrinsic safety parameter | Power port: Ui = 15V DC, Ii= 400mA, Pi = 1.5W, Ci = 3.63μF, Li = 0mH; Signal port: Ui = 7.14V DC, Ii= 147mA, Pi = 260mW, Ci = 32.6μF, Li = 0mH; |
Associated apparatus | WB-GSB03 safety barrier |
Explosion proof grade | Ex ia IIA T4 Ga, Ex II 1G Ex ia IIA T4 Ga |
Protection grade | IP68 |
Applicable medium | Gasoline, kerosene, diesel, Ethanol gasoline, Methanol gasoline, Approved light oil |
Definition of wires | Blue - Power + : Brown - RS485A: White - RS485B: Black - Power - |
Communication address | 6 digits, see the"Manufacturing code"or S/N code on probe nameplate, this is also Probe ID in communication with console and FMS |
Dimension (L*W*H) | 243*12*12cm, 5kg |