Description
BAC series switch b5attery chargers use the latest switch power .
devices. Designed according to the charge characteristics of the .
lead-acid battery for starting generators, BAC chargers are suitable for the long time
supplement charge(floating charge) of the lead-acid battery. The maximum charging
current is 6A for 12V and 10A for 24V.
Category | Items | 12V | 24V |
Model | BAC | BAC-1206 | BAC-2403/2405/2410 |
Input | Nominal input voltage | AC(100~240)V |
Max input voltage | AC(90~305)V |
Frequency | 50Hz/60Hz |
Max input current | 2.5A | 2.5A/2.5A/4A |
Efficiency | >85% |
Output | Charging current | 4A~6A,error±2% | 2A~3A/5A/10A,error±2% |
Factory charging current | 6A | 3A/5A/10A |
Max output power | 135W | 135W/135W/290W |
Min output voltage | 7.5V |
No-load output voltage | 13.8V,error 1% | 27.6V,error 1% |
No-load consumption | <3W |
Insulation | Insulation resistance | When between input and output, output and shell are both DC500V 1min, the insulation resistance RL≥50MΩ |
Insulation voltage | When between input and output, output and shell are both AC1500V 50Hz 1min, the leakage current IL≤3.5mA |
Working conditions | Working temperature | (-30~55)ºC |
Storage temperature | (-40~85)ºC |
Working humidity | 10%RH~95%RH(no condensation) |
Structure | Weight | 0.65kg | 0.65/0.65/1.15kg |
Dimensions(L*W*H mm) | 143*96*55(3A/5A/6A); 205*146*55(10A); |
PERFORMANCE FEATURES1. Designed in switch power structure. Wide range of the input voltage. Small volume,
light weight and high efficiency.
2. Automatic charge using the 2-stage charging method(i.e., constant current first and
then constant voltage). The process
is in full accordance with the battery charging characteristics, and can prevent
overcharging of lead-acid battery and maximize battery life.
3. Have protection functions for short-circuit and reverse connection.
4. Charging voltage and current can be regulated by potentiometer on site.
5. LED status display: AC power indication, charging indication
6. Horizontal instllation. Easy to install.
CONFIGURATION
Voltage regulationWhen regulating voltage on site, it is needed to disconnect the battery from the charger.
Measure the charger output voltage while regulating the voltage potentiometer (VOLT)
until the appropriate value is reached.
Current regulationConnect the output to the battery. Measure the charging current when the charging
voltage is not higher than 25.0V (12.5V). Regulate the current potentiometer (AMP) to
set the appropriate charging current.
The output current can also be estimated according to the current potentiometer scale.