Detailed types of the K800 series Fixed Gas Detector:
K800-[gas type]-[mount pattern]
N: with non-dispalay
D: with LED display
DA:alarm with light and sound
>>>Technical Specification:
Power supply | 24VDC |
Output signal | 4-20mA standard industrial signal output |
Operating temperature | -20°C~+50°C |
Display | Backlight LED |
Relative humidity | 15%~90% RH (non-condensing) |
Atmospheric pressure | 86~106Kpa |
Explosion-proof grade | Exd IICT6 |
Warranty | 1 year |
Power supply | 24VDC |
Output signal | 4-20mA standard industrial signal output |
Operating temperature | -20°C~+50°C |
Display | Backlight LED |
Relative humidity | 15%~90% RH (non-condensing) |
Atmospheric pressure | 86~106Kpa |
Explosion-proof grade | Exd IICT6 |
Warranty | 1 year |
No. | Detection gas | Range | Accuracy | 90% response time | Min readout | Low/high alarm |
1 | PH3 | 0-5-2000ppm | ±5%(F.S) | ≤25s | 0.01ppm | 0.3/5ppm |
2 | O2 | 0-30% | ±5%(F.S) | ≤15s | 0.1%vol | 18.0%/23.0% |
3 | LPG(LEL gas) | 0-100%LEL | ±5%(F.S) | ≤5s | 1%LEL | 25.0%/50.0%LEL |
4 | CO | 0-1000 ppm | ±5%(F.S) | ≤25s | 1 ppm | 50ppm/100ppm |
5 | H2S | 0-100 ppm | ±5%(F.S) | ≤30s | 1 ppm | 10ppm/20ppm |
6 | CH4 | 0-100%LEL | ±5%(F.S) | ≤5s | 1%LEL | 25.0%/50.0%LEL |
7 | NH3 | 0-100ppm | ±5%(F.S) | ≤50s | 1 ppm | 25 ppm /50 ppm |
8 | O3 | 0-20ppm | ±5%(F.S) | ≤60s | 0.01ppm | 0.2ppm/0.4ppm |
9 | CI2 | 0-20 ppm | ±5%(F.S) | ≤30s | 0.1 ppm | 1 ppm /10 ppm |
10 | H2 | 0-1000 ppm | ±5%(F.S) | ≤60s | 1 ppm | 50 ppm /100 ppm |
11 | SO2 | 0-100 ppm | ±5%(F.S) | ≤30s | 0.1 ppm | 2 ppm /10 ppm |
12 | NO | 0-250 ppm | ±5%(F.S) | ≤60s | 1 ppm | 25ppm/50 ppm |
13 | NO2 | 0-20 ppm | ±5%(F.S) | ≤25s | 0.1 ppm | 3ppm/10ppm |
14 | Infrared CO2 | 0-5%vol | ±5%(F.S) | ≤60s | 0.1%vol | 1%vol/2%vol |
15 | Infrared CH4 | 0-5%vol | ±5%(F.S) | ≤60s | 0.1%vol | 0.1%vol/0.15%vol |
16 | Infrared C3H8 | 0-5%vol | ±5%(F.S) | ≤60s | 0.1%vol | 0.1%vol/0.15%vol |