Series | Code | Name | Setting range | Remark | Ex-Factory | |
First Menu | 0 | - | Appointed data | Determined by and | Press∧or∨for 3 second and set the temperature setting value you need | - |
1 | AL | High/Low-limit alarm | Determined by and | - | Random | |
2 | SC | Measurement deviation | -20.0~20.0 | Measuring value can be modified through increasing or decreasing this data. | 0 | |
3 | P | Proportion time | 0~99.9~200 | When the P↑,the proportion and differential function↓;If the P↓,the proportion and differential function↑ When P=0,the meter is ON/OFF control. | 15.0 | |
4 | I | Calculus time | 0~999 | It's used to adjust static difference. To increse it,the static difference will be reduced, but if it is too high, the static difference will drift instability. | 240 | |
5 | d | Differential time | 0~200 | 30 | ||
6 | t | Control period | 2~120S | When it leaves factory, SSR is 2s; Relay is 20s. When P=0, it makes no sense. | 20 | |
7 | Hy | Main control by drop in level | 0.1~50.0 | It only controls at ON/OFF | 1.0 | |
8 | At | Parameter setting itself | / | OFF_shut itself function ; ON_open itself function Select ' ON'only can adjust for one time,and then turn back to 'OFF ' | OFF | |
9 | Loc | Electronics lock | 0~50 | Loc=0 all the parameter can be revised Loc=1 only the appointed data can be revised | 0 | |
Second Menu | 10 | Loc | Electronics lock | 0~50 | idem | 0 |
11 | Sn | Input type | - | CU50\PT100\K\E\J(\T; | K | |
12 | dIL | Set lower limit | dIL≤dIH | CU50(-50~150)\ PT100(-80~600)\ K(-30~999)\E(-30~700)\ J(-30~900)\T(199~400) | 0 | |
13 | dIH | Set upper limit | 400 | |||
14 | PF | Filt modulus | 0~50 | It is the software filter constant of measurement sampling.The constant ↑,the measurement antijamming capability↑,but the measurement speed and system response time ↓ | 20 | |
15 | COL | System function choice | ON/OFF | ON:positive control(cooling control) OFF:reverse control(heating control) | OFF |