KONNEN AIR SOURCE HEAT PUMP, EVI AIR TO WATER HEAT PUMP ,WORKING TEMPERATURE -30° C--43° C.
* Low-temperature cycle type with great performance of environmental protection, low operating costs, outstanding energy savings, safety and so on.
* Improving performance under cold temperature, safe and reliable - air injection & increase enthalpy products to achieve heating operation whthin-25 ° C - 43 ° C, increaseing the compressor heating capacity in the cold, rising nearly 20% heating capacity under-10 ° C, leading to "strong hot and cold" era. When the temperature is as low as -20 ° C the heat pump can start running and get good effect of hot water supply.

Scope: Hotels, guesthouses, entertainment sauna center, body building club, beauty salon, bathing centers, hospitals, factories, restaurants, dormitories, residential central heating and other hot water useing places.

1, High efficiency
* Energy efficient - the unit uses the world advanced technology - air injection & increase enthalpy systems, high efficiency heat exchanger technology, technology, air injection and enthalpy increase, higher COP in low temperature.

2, Safe and reliable
* Safe and reliable -useing of microcomputer for automatic control, control and fill constant temperature of hot water and ensure water temperature in water tank according to the water level, temperature, which can meet the requirement for all day water using in any time, water and electricity are separated, safe and reliable.
* Microcomputer controlled power-off memory, automatic fault detection, protection timely, more reliable, use more confidence.
* Easy installation - remote controller installation, strong and weak electric be completely separated, operation securely.

3, Energy saving
* Use R417A, R407C refrigerant, ozone depletion factor is zero, green, to meet the national environmental requirements, to eliminate the forbidden risk. (Optional refrigerant R22)
WE SUPPLY OEM SERVICE!

KONNEN NEW FACTORY(HEAT PUMP + WATER TANK + CONTROLLER):

WHY US:

KONNEN NEW PROJECTS:

WORLD FAMOUS BRANDS WE COOPERATED FOR OUR HEAT PUMPS:

KONNEN HEAT PUMPS LOADING:

PARAMETERS TABLE:
A02U series( EVI air source heat pump low temperature type)                                                                                                                          EVI-150307 
 EVI3P-S5EVI5P-S5EVI10P-C24EVI14P-C24EVI20P-C48EVI30P-C48EVI40P-C96EVI48P-C96
Normal conditionHeating capacitykW1219365175105145165
Input powerkW2.80 4.40 8.20 11.85 17.10 24.10 33.20 38.10 
Input currentA5.30 8.60 14.80 22.58 33.00 45.10 62.50 72.30 
COP/4.29 4.32 4.39 4.24 4.39 4.36 4.37 4.33 
Nominal  conditionRated heating capacitykW9.50 15.00 30.00 42.00 60.00 90.00 120.00 144.00 
Rated input powerkW2.60 4.10 8.10 11.34 16.10 24.50 32.50 39.30 
Rated input currentA5.20 8.20 15.30 21.42 30.20 46.00 61.10 73.60 
COP/3.65 3.66 3.70 3.70 3.73 3.67 3.69 3.66 
Low temperature conditionHeating capacitykW5.50 8.80 17.50 24.50 36.50 52.50 70.00 84.00 
Input powerkW2.26 3.65 7.30 10.22 15.10 21.60 29.10 34.90 
Input currentA4.29 6.93 13.00 18.20 28.10 40.80 54.80 65.70 
COP/2.43 2.41 2.40 2.40 2.42 2.43 2.41 2.41 
Maximum input power/currentkW/A3.61/6.925.71/11.2010.62/20.7515.42/30.0822.27/43.3631.38/61242.92/83.6251.5/100.3
Rated hot water output temperatureºC55
Maximum hot water output temperatureºC60
Rated hot water produce capacityL/H204.25322.56459031290193525803096
Power supply3N 380V/50Hz
CompressorTypeFully closed scroll type
Start modeDirectly start
Water side heat exchangerTypeShell & coil(tube) heat exchanger
Water flowM3/h2.1 3.3 6.0 8.9 12.9 18.0 24.9 29.9 
Water pressure dropKPa≤50≤55≤60≤60≤65≤65≤65≤65
Pipe sizeDN2525323250656580
Middle heat exchangerTypeBrazed plate type heat exchanger
Protections1. High pressure and low pressure protection,  2. Anti-freezing protection, 
3. High temperature protection, 4. Too big of the water temperature difference for outlet and inlet protection, 
5. Overload protection,  6. Lack phase protection, 
7. Reverse phase protection, etc.. 
NoiseDB(A)≤55≤58≤60≤60≤65≤73≤74≤78
Unit dimensionsmm835×410×13301000×1000×18581000×2050×19002000×2050×1980
Package dimensionsmm910*480*13701150*1150*22502200×1150×23002300×2100×2300
WeightKG11517535542562085512501300
Testing condition: 1. Normal condition: dry bulb 20ºC, wet bulb 15ºC; initial water temperature 15ºC, end water temperature 55ºC.
                         2. Nominal condition: dry bulb 7ºC, wet bulb 6ºC; initial water temperature 9ºC, end water temperature 55ºC.
                         3. Low temperature condition: dry bulb -12ºC, wet bulb -14ºC; initial water temperature 9ºC, end water temperature 55ºC.
 
The above parameters may have some differences from the final product because of products updating, so above information is not the provision of any business contract. Please refer to final product lable when buy, or refer to us for any information. Our company keeps the right to interpret.