Technical parameter

Rated capacity (KVA): 10~2400 KVA, 3~500 KVA

Input current (A): Correlation to the rated capacity

Input voltage (V): 380VAC+/-20% optional, 220VAC+/-20% optional

Output voltage (V): 380VAC+/-5% optional, 220VAC+/-5% optional

Phase number: Three phase single phase

Insulated strength: 2000V/1 Min does not have the puncture

Time for response: ≤ 1.5s (input fluctuation within 10%)

Efficiency: ≥ 98%

Waveform distortion: ≤ 0.1%

Working frequency (Hz): 50~60

Constant voltage precision: +/-5% adjustable

Concerning that most imported assembly line equipments have different service voltage with domestic electric network, our company designed this model of voltage regulator. It combines voltage regulation and transformation, enjoying the features of small volume, high precision of voltage regulation, swift speed of response, impressive ability of anti load impact, good stability, and flawless protection facility.
ModelDBWSBW
Capacity (KVA)1000
Input voltageSingle Phase: 220V±20%
Three Phase:380V±20%
Output voltageSingel Phase:220V- 230V(Adjustable)
Three Phase: 380V - 405V(Adjustable)
Output accurac y±1-5%  Upon your request
Frequency50Hz
Insulation resistance≥2MΩ
Noise<55dB
Voltage regulation modeIndependent phase regulation
Wave deformationNil
Insulation class of transformerH class
Wire systemSingle Phase
Three Phase : 3-Phase-4-wire-system   or 3-Phase-5-wire system
Operation time≥80,000 hours
Long Life Time Carbon brush 140,000 times with only about 0.01mm roller carbon brush abrasion
Method of voltage regulationRegulation transformer with servomotor
Insulated strengthSingle phase: 2000V/1min without puncture
Three phase: 2500V/1 min without puncture
Package MaterialCarton for batch volume, Wooden packing for small volume
Efficiency>96%
HousingIP20(Indoor)IP55(Outdoor)
Electrical safetyCE equivalent
Operating temperature-20 °C to +50 °C
Altitude<1000m
Relative Humidity<90%
Material of Sliding coilCopper, and inner and outer winding both
 FunctionsMalfunction protection;Short-circuit protection,
Lack Phase protection; Manual bypass,Safe start
Alarm and silence, Under/Over voltage Protection
Optional  FunctionsAuto Power-on;Isolation Transformer;
Surge Protection;Remote Monitor
 
PhaseModelCapacity(KVA)Dimension(H×W×D)mmCabinet(QTY)
Single PhaseDBW-10101020×300×7001
DBW-15151020×300×7001
DBW-20201020×300×7001
DBW-30301020×300×7001
DBW-50501120×380×7501
DBW-80801220×400×7801
DBW-1001001220×400×7801
DBW-1501501420×450×9301
DBW-2002001420×450×9301
Three PhaseSBW-10101020×300×7001
SBW-20201020×300×7001
SBW-30301020×300×7001
SBW-50501120×380×7501
SBW-80801220×400×7801
SBW-1001001220×400×7801
SBW-1501501420×450×9301
SBW-2002001520×520×9801
SBW-3003001720×600×13801
SBW-5005001860×720×15801
SBW-8008001860×900×10801
SBW-100010001860×900×10802
SBW-150015001860×900×10803
SBW-200020001860×900×10803