Rated Voltage | 12V |
Numbers of cells | 6 Cells |
Capacity | 150Ah@10hr-rate to 1.80V per cell @25°C |
Internal Resistance | Approx. 4mΩ |
Terminal | F1/F2 |
Max. Discharge Current | 2250A(5s) |
Short Circuit Current | 7500A |
Max. Charging Current | 37.5A |
Reference Capacity | C10 150AH/C3 108.7AH/C1 82.4AH |
Design Life | 10~15 years |
Float Charging Voltage | 13.6 V~13.8 V @ 25°C, Temperature Compensation: -20mV/°C/Cell |
Cycle Use Voltage | 14.4 V~14.9 V @ 25°C, Temperature Compensation: -30mV/°C/Cell |
Operating Temperature Range | Discharge: -15°C~50°C, Charge: 0°C~40°C, Storage: -15°C~40°C |
Normal Operating Temperature Range | 25°C±5°C |
Self Discharge | Less than 3% at 25°C per month |
Container Material | A.B.S. UL94-HB, UL94-V0 Optional. |