Three-Phase Automatic Recovery (RECLOSERS) Switches for 13.8 Kv Systems

Min.Order: 1
Product origin: Ningbo, Zhejiang, China
Infringement complaint: complaintComplaint
US$ 8000

Description






Applicable Standards

The Quality Management System shall be ISO 9001 Certified. The equipment shall comply with the latest revision of the following standards:

ANSI/IEEE C37.60 IEEE Standard Requirements for Overhead, Pad-Mounted, Dry-Vault, and Submersible Automatic Circuit Reclosers and Fault Interrupters for AC Systems.

IEC 62271-111 High-voltage switchgear and controlgear -Part 111: Automatic circuit reclosers and fault interrupters for alternating current systems up to 38 kV.

ISO 1461 Hot dip galvanized coatings on fabricated iron and steel articles- Specifications and test methods.

IEC 60721-2-1 Classification of environmental conditions Part 2-1: Environmental conditions appearing in nature  Temperature and humidity

IEC 60529  Degrees of protection provided by enclosures (IP Code)

IEC 60815-3 Selection and dimensioning of high-voltage insulators intended for use in polluted conditions - Part 3: Polymer insulators for a.c. systems.

IEC 61109 Composite insulators for a.c. overhead lines with a nominal voltage greater than 1000 V - Definitions, test methods and acceptance criteria.

IEC 60870-5-104 Transmission Protocols, Network access for IEC 60870-5-101 using standard transport profiles.

IEC 60410  Sampling plans and procedures for inspection by attributes
 

No.SpecificationsComply
YesNo
          1The Recloser to offer is automatic three-phase, with electric control based on microprocessor to be installed in pole and used in distribution systems of 7.9 / 13.8Kv, 60 Hz, in multi-terrain starYES 
          2Comply with NEMA SG-13, ANSI C37.60, ANSI C37.61 and ANSI C37.90 standards, or internationally recognized equivalent standards used by other countries in which case they must attach a copy of the respective standard in Spanish language. EnglishYES ,IN EGNLISH 
          3The manufacturing company is certified with ISO 9001.YES 
          4The nominal capacity, minimum current is 630 continuous amperes for 14.4 Kv.YES 
          5Required nominal voltage is 13.8 Kv, 60Hz.YES 
          6Vacuum interruption or vacuum chambers are encapsulated in solid insulationYES 
          7Solid dielectric insulation has no toxic components that present a risk and affect the environment.YES 
          8The maximum accepted total weight is 400 poundsYES 
          9The maximum interruptive capacity is 12.5 symmetric kilo-amperes for 14.4Kv. applied standard, ANSI C37.60 or IEC equivalent.YES 
          10The basic impulse level (BIL) for 14.4 Kv is 110 Kv, standard applied ANSI C37.60 or IEC equivalent.YES 
          11The unit has a mechanism for manual operation from the ground by means of a pole.YES 
          12It is capable of performing a sequence of 1, 2, 3 or 4 operations with automatic reclosing before disconnecting in a defined manner in the last operation and adjustable for any combination of slow and fast operation curves. The contacts remain open after the last operation.YES 
          13Have operations counter, total and phase, allowing to be read while the Recloser is in serviceYES 
          14The minimum mechanical life in number of operations must be 10,000.YES 
          15To have easy to read indicator of open or closed position and locking mechanism to prevent reclosing.YES 
          16The power and output terminals must be bimetallic screw with capacity for conductors of 9 to 22 mm in diameter and a grounding connector of the equipment, with cable capacity of 11 mm in diameter.YES 
          17The tank must have two hooks or another suitable element to be able to lift it, appropriate supports to fix it to the post with clamp or bolt to an appropriate structure for it. In addition, all bolted connections (tank, cover, bushings), must include the included stainless steel bolts.YES 
          18The support structure for mounting the Recloser to the pole must be supplied; It must also include the supports and accessories necessary for the assembly of the six (6) lightning arresters type valve according to the nominal voltage of the equipment, and also include the supply of these lightning rods with the equipment.YES 
          19The closing of the main contacts must be achieved through a single operation of a mechanism operated by a high voltage coil, which is fed through two phases of the input line, or also using closing mechanisms for stored energy , magnetic actuators, low voltage coils, etc.YES 
The recloser must be closed in both directions (side of the source or side of the load), using an internal mechanism to perform this operation
          20The Recloser must have at least 3 current transformers installed in the bushing on the load side of the recloser.YES 
          21The Recloser includes at least three (3) TP sensors, incorporated into the equipment.YES 
          22It must include a transformer reducing voltage not greater than 1 KVA, capable of permanently powering the electronic control. (The transformer must be small to place it in the same structure of the equipment) It should be supplied with its respective protective equipment:YES1
-1 potential transformer for 7,967 KV / 120 volts for control power. 
-1 circuit breaker for 10 kv and 
-1 Pararrayo for 10 KV 
          23The bushings must be made of porcelain, epoxy resins or high density polymers, hydrophobic resistant to ultraviolet rays to operate with high levels of humidity, high salt contamination and aggressive environments.YES 
          24The units must have a data plate indicating at least the following:YES 
Name of the manufacturer
Brand, model and serial number
Rated voltage
Rated capacity in amps
Interruptive capacity
Date of manufacture and number of tender
Total weight
          25The manufacturer must propose a means to permanently mark the equipment as property of ENEE  
ELECTRONIC CONTROL BASED ON MICROPROCESSOR
          26It must be located in a weather-proof enclosure and may be installed remotely using a 5-meter long multiconductor cable with plug-in connectors. The box must have external hooks to fix it to the post with screws, bolts or clamps.YES 
          27It must have an event recorder that can be interrogated to obtain operations data and type of failures.YES 
          28It  must have the settings and accessories for the selection of the number of reclosing operations required to be locked, selectable between 0,1,2,3 times according to the programming of the microprocessor.YES 
          29It must have the settings and accessories for the selection of the sequence of trip by earth current, to select the number of fast operations, between 0,1,2,3,4 according to the programming of the microprocessor.YES 
          30It must have closing delay adjustment, with multiple adjustment capacity between 1 to 60 seconds, for the first, second and third reclosing. The first shot must have a setting for instant firing of 45 cycles maximum.YES 
          31It must have the settings and accessories for the selection of operating curves for ground fault, it must have a selector for fast operation and another for slow operation, according to the programming of the microprocessor.YES 
          32It must have the settings and accessories for the selection of operating curves for phase failure. It must have a selector for fast operation and another for slow operation, according to the programming of the microprocessorYES 
          33It must have the adjustments and accessories so that the operating curves are compatible to coordinate with any type of Recloser and relays type CO 11 or similar. The offer must be accompanied with all available curves to apply the most convenient to our systemYES 
          34It must have the settings and accessories so that the selection of the time delay is between 10 to 180 seconds for resetting after successful reclosing during an operation sequence, according to the programming of the microprocessor.YES 
          35Must have selection of minimum tripping current due to ground fault is adjustable, according to the programming of the microprocessorYES 
          36It allows the selection of the minimum tripping current due to phase failure, which can be adjusted according to the programming of the microprocessor.YES 
          37It has a switch to block the tripping of ground fault current.YES 
          38It has a switch to block the reclosing in case of an opening.YES 
          39It has a switch for supervisor controlYES 
          40The control shall include the external input and output modules (dry contacts) with 12 volt operating voltages for execution of configurable signals or own voltage supplied by the control.YES 
 It must at least include the following contacts:
 Outputs: opening, closing, red card; Inputs: open state, closed state, lack of power ac etc).
          41It has a switch to open or close the Recloser from the control cabinet. The close command must momentarily alter the instantaneous trip setting to avoid triggering as a result of transient overcurrents that occur when a load is energized.YES 
          42It has a power source for the control system and operations to start an opening or closing Recloser, using non-rechargeable lithium cells, or rechargeable nickel-cadmium or lead-acid, with charger powered from a 120-vac source, by means of a voltage reducing transformer. Backup batteries must guarantee the autonomy of electricity supply for a period of not less than 24 hours.YES 
          43It has an operations counter due to phase failure and ground fault.YES 
          44It has, when required, an easy-to-operate mechanism to change the protection scheme to a pre-set schedule by the operator.YES 
          45Must have a sequence coordination selector mechanism between two series Reclosers  
          46It must have facilities for opening or closing telecontrol, as well as blocking, reclosing and interrogation.YES 
          47It is equipped with an RS-232 type connector for connection to a commercial PC that allows calibration, programming and data collection using a personal computer of the commercial type and with a screen for reading, programming and verification of data.YES 
 Likewise, it will be equipped with light signal devices that allow to identify locally, among other things, the operating status of the electronic control system, the type of fault and the failed phase
          48It is supplied with a mounting cable, of suitable length to connect the control to the Recloser. (5 meters long)YES 
          49It has a communication port to connect the PC, and to be able to read data; This port is independent of the communications port used for monitoring and control.YES 
          50It is supplied inside with an AC protection breaker for power inputs of the control of a power outlet.YES 
          51It has a non-resettable counter for opening operations.YES 
          52It has a remote command by means of radio modem and wireless modem signals and is equipped with a remote terminal unit (RTU) that can be programmed with modern protocols and in which DNP3.0 (RS-232) is included without exception. and TCP / IP)YES 
          53The Remote Terminal Unit allows communication through communication ports: RS232, and at least one port for Ethernet |YES 
          54The remote control allows the control to be compatible with an automated distribution system (SCADA), which will allow remote control and monitoring with which It can perform at least the following:YES 
 Information on the status of the device (open restorer, closed restorer, blocked control, normal state control, supervision switch status, operation without reclosing, power A.C connected, power line maintenance, etc.)
 Information on operating protections: identification of phase A fault, identification of phase B fault, phase C fault identification, neutral phase identification and identification of earth sensitive fault.
 Instantaneous value of currents and voltages per phase and other energy parameters.
 Output commands that allow operations to be performed remotely (opening restorer, closing restorer, changing settings, activating online maintenance energized / deactivating maintenance on energized line, do not reclose etc).
          55It includes a power source of Vcc located in the control cubicle that also has space for a radio modem. The reclosers can be remote controlled from the SCADA control center.YES 
          56If the control of the Recloser requires a special programming reader to collect data and / or program the control; must have the necessary software to carry out the programming, interrogation and capture of data by a personal computerYES 
          57The supplier must deliver with the equipment a minimum of three operating manuals, programming, maintenance and test equipment, as well as the electrical control diagram, written in Spanish and English. In addition, it must include the equipment Installation and programming software.YES 
 
          58Others.YES 
 It must include in the offer a course to be taught in the city of Tegucigalpa, for a minimum of three days. The exhibitor must be a technician authorized by the manufacturer of the equipment for this purpose. The course should address issues about maintenance, test settings, programming and installation of equipment; The integration of the control should also be included, to SCADA SHERPA of the Control Center and Tele distribution management (DNP3.0 communications protocol). The program and content of the course to be taught must be indicated in the proposal.
 Training should be included in the Tegucigalpa and San Pedro Sula sites.
 - 1 day Tegucigalpa (20 people): General equipment and basic functionalities of the team. Directed to personnel distribution
 - 1 day Tegucigalpa (8 people): SCADA mapping and team integration tests at SCADA Distribucion. Directed to SCADA hardware and software personnel.
 - 1 day San Pedro Sula (20 people): General and basic functionalities of the team. Directed to personnel distribution.
 Note: This course would apply for Reclosers of 13.8 KV and 34.5 KV