This FACP uses two buses mode, monitoring up to 242 control points of every loops. Wall mount design makes it easy to use and operate. It is compatible with complete range of our electronic coding, remote control coding series' intelligent detectors, manual call point, input module, I/O module, etc. The fire protection system can be divided into controller, detectors, modules and operation terminals. The FACP is combined with main control module, driver board and communication board.
Main board is the core of the FACP, which contains CPU and interfaces to other main and optional components of the system. It also has output of fire alarm and fault. It is fixed on the cabinet's door and contains LCD display, indicators, operation keys, 6 direct activation keys, 24 loop linkage control keys, interface of printer and communication interface of the mother board .etc.
The main board is the control center of the FACP. The hardware circuit composites of SCM S344BOX which is the center of the FACP, extended with some memory chip card, keypad, LEDs and printer etc. The SCM communicates data (send and receive orders), analyzes date, judges status and sends alarms (sounder/strobe indicate, LED display, printer records, black box log, 485 communication, RS232 communication etc) via its asynchronous serial communication interface, loop driving card and direct control output button. The SCM can also receive the key operation information and login in relevant menu interface; inquire or set the characteristic of the FACP, status information; receive the power supply working status and send out relevant information. All functions stated above are controlled by the software which built-in the memory Chip card.
2.4 Main Technical Characteristi 2.4.1 Power Supply: AC Power(Main Power): Input Voltage ~ 220VAC ( 175~ 245VAC) Standby Power: Standby power supply with different capacity should be configured according to different device points. 2.4.2 Operating Environment: Operating temperature: 0ºC ~ +42ºC Relative humidity: ≤95%, Non-condensing 2.4.3 Capacity: Floor type: 64 Loops; Control Points of Each Loop: 242. 2.4.4 Display: LCD display (Mode: HY-320240) 2.4.5 Dimension( L x W x H ): 420mm x130mm x 470mm; 2.4.6 Wiring Requirement ·For 485 communication cable and fire alarm bus cable, it is recommended to use UTP RVS2×1.0 MM 2OR RVS2×1.5 MM 2 twisted-pair cable; When environmental interference is heavy, it is better to use RVSP2×1.0MM shielded twisted-pair cable. ·It is forbidden to put the 485 communication cable, telephone line and fire alarm bus cable in one multi-core cable.