Features:
Specifications:
* Max voltage output: refer to following table
* Output frequency: 0.1Hz, 0.05Hz, 0.02Hz
* Measurement accuracy: 2.5%
* Positive and negative voltage peak errors: < 2.5%RDG+0.3%FS
* Voltage wave form distortion: <3%
* Insulation resistance measurement error: <2.5%
* Leakage current measurement error: <2.5%
* Power supply: AC220V ± 10%, 50Hz/60Hz
* Environment temperature: 0~50°C
* Humidity: ≤85%RH
Type | Output Voltage/ Current | Load Capacity | Control Unit | Booster | Fuse Tube | ||
Frequency/ Capacitance | Dim. (cm) | Wt (kg) | Dim. (cm) | Wt (kg) | |||
VLF-30 | 30KV/20mA | 0.1Hz ≤ 1.1uF 0.05Hz ≤ 2.2uF 0.02Hz ≤ 5.5uF | 28× 37× 22 | 4 | 33× 18× 34 | 25 | 5A |
VLF-40 | 40KV/30mA | 0.1Hz ≤ 1.1uF 0.05Hz ≤ 2.2uF 0.02Hz ≤ 5.5uF | 28× 37× 22 | 4 | 35× 20× 36 | 35 | 6A |
VLF-50 | 50KV/40mA | 0.1Hz ≤ 1.1uF 0.05Hz ≤ 2.2uF 0.02Hz ≤ 5.5uF | 28× 37× 22 | 4 | 37× 24× 39 | 45 | 7A |
VLF-60 | 60KV/50mA | 0.1Hz ≤ 1.1uF 0.05Hz ≤ 2.2uF 0.02Hz ≤ 5.5uF | 28× 37× 22 | 4 | 33× 18× 34 33× 18× 34 | 25+25 | 10A |
VLF-70 | 70KV/55mA | 0.1 Hz, ≤ 0.5µ F 0.05Hz, ≤ 1.0µ F 0.02Hz, ≤ 2.5µ F | 28× 37× 22 | 4 | 33× 18× 34 35× 20× 36 | 25+35 | 10A |
VLF-80 | 80KV/60mA | 0.1 Hz, ≤ 0.5µ F 0.05Hz, ≤ 1.0µ F 0.02Hz, ≤ 2.5µ F | 28× 37× 22 | 4 | 33× 18× 34 37× 24× 39 | 25+45 | 12A |
When carrying out 10KV cable test, one-phase test is strongly suggested. The voltage shall be 18KV and the frequency shall be 0.1Hz(recommend), 0.05Hz(recommend),0.02H(The boost process is slow), 0.01Hz(The boost process is very slow, 10-40 minutes, suitable for cables over 10 kilometers). The manual mentioned load capacity is the theoretical value, the scene 10KV cable length can reach 3-20 km.
When carrying out 35KV cable test, one-phase test is strongly suggested. Voltage is set to 60KV (general requirements)-78KV (according to the rules needed) and the frequency is set to 0.1Hz(recommend), 0.05Hz(recommend), 0.02Hz(The boost process is slow) and 0.01Hz(The boost process is very slow, 10-40 minutes, suitable for cables over 10 kilometers). The manual mentioned load capacity is the theoretical value, the scene 35KV cable length can reach 3-15 km.