0.1Hz Vlf High Voltage Generator AC Hipot Tester for Cables, Gis 30kv/40kv/50kv/60kv/70kv/80kv/90kv/100kv Vlf Testing Machine

Min.Order: 1
Product origin: Wuhan, Hubei, China
Infringement complaint: complaintComplaint
US$ 1000 ~ 10000

Description
VLF AC HIPOT TEST SET
EPVLF-80/1.1


General Information:
VLF stands for Very Low Frequency. VLF is generally considered to be 0.1 Hz and lower, its major application is for testing solid dielectric cable, transformers, motors, generators, switchgear and other electrical apparatus.

A VLF hipot is just an AC output tester but with an output frequency of 0.1 Hz or lower rather than 50/60Hz. Although the frequency is very low, it is still an alternating current with polarity reversals every half cycle. At 0.1 Hz output, rather than 60Hz, it takes 600 times less current and power to apply an AC voltage to a capacitive load, like a long cable.


Features:
  • Adapts microprocessor controlled, can realize voltage set-up/down, measuring and protecting automatically. Manual intervention is allowable even during the auto voltage boosting.
  • Portable, easy to move.
  • Large LCD can display waveform clearly, and test report can be printed. Built-in printer.
  • The data of current, voltage, and waveform can be sampled at HV side.
  • A high voltage output protective resistor is provided in the voltage boost body in the design and this eliminates the need of additional protective resistor connected outside.
  • Closed-loop negative feedback circuit is adopted. No capacity rising during outputting.
  • Over voltage and current protection: When the output is beyond the limitation, the control unit will shut itself down within 20ms.

Specifications:
Peak voltage:80kV
Output frequency: 0.1Hz, 0.05Hz and 0.02 Hz (selectable)
Fuse: 20A
Maximum load capacity: 1.1μ[email protected], 2.2μ[email protected], 5.5μ[email protected]
Measurement accuracy:3%
Voltage positive and negative peak error:≤3%
Voltage waveform distortion:≤5%.
Working environment:Temperature: -10ºC-+40ºC, 85%RH.
Indoor or outdoor, 
Weight: Control unit:4kg
HV unit: 50kg
Power supply:220V 50Hz
The capacitance of the tested object shall not exceed the maximum rated capacitance of the instrument.

More details on VLF testing 30/40/50/60/70/80/90kV please contact EPHipot, we have professional tech team to design correctly designed products and systems.











Product Tag:
Related categories:
Scroll to Top