ACREL smart din rail motor overload protector / protection relay with leakage current
Smart Motor Protector ARD2 Series (hereinafter referred to as Protector) can protect the motor from timeout startup,overload, phase failure, unbalance, under-load, earth leakage, blocking, short circuit, external fault and other abnormalities.
During the running and provide the SOE fault event recorder to help maintenance stuff find causes.
It is applicable for coal mines, petrochemical industry, metallurgical industry, power industry, shipbuilding, civil building and other fields.
It is with RS485 remote communication interface and the DC 4-20mA analog output, which is convenient to form a
network system together with control machines like PLC and PC to realize the remote monitoring of motor.
Functions of model ARD2F-25+90L
Functions of model ARD2F-25,
*rated current range:6.3-25A
*protect motor from timeout startup,overload, phase failure, unbalance, under-load, earth leakage, blocking, short circuit, external fault and other abnormalities
during running
*Optional functions,
Start up control(K,Q)
alarms(J)
9DI(K)
RS485 modbus RTU(C)
2 channel modbus RTU(2C)
Leakage current protect(L)
4-20ma analog value output(M)
2DI,1 relay(K)
SOE event record(SR)
Temperature measure(T)
Voltage(U)
Display unit(90L)
Anti electricity(SU)
tE time protect(tE)
Energy(Ep)
Order Notes:
Pls inform setting current range,motor power,auxiliary power and extra functions before ordering.
Data sheet
echnical data of motor protector ARD2F-25 | ||
Auxiliary power supply of protector | AC85V~265V/DC100V~350V, power consumption ≤7VA | |
Rated working voltage of motor | AC380V/AC660V, 50H/60Hz | |
Rated working current of motor | 1A(0.1 ~9999) | Small specific current transformer |
5A(0.1 ~9999) | ||
1.6A(0.4A-1.6A) | ||
6.3A(1.6A~6.3A) | ||
25A(6.3A~25A) | ||
100A(25A~100A) | ||
250A(63A-250A) | Specific current transformer | |
800A(250A~800A) | ||
Relay output contactor, rated load capacity | 4-way,AC250V, 3A, DC30V, 3A | |
Switching input | 2-way, optical isolation | |
Communication | RS485 Modbus | |
Volume of SOE event recorder | 8 events | |
Environment | Working temperature | -10ºC-55ºC |
Storage temperature | -20ºC-65ºC | |
Relative humidity | 5%-95%, no dew | |
Altitude | ≤2000m | |
Class of pollution | 2 | |
Protection level | IP20 |
250 | 1 | 63~250 | 55~132 |
800 | 1 | 250~800 | 160~440 |