Model | 13060 | 13100 | 33150 | 33300 | 331000 | 332000 | 334500 | 336000 | 338000 | 3316000 | |||
Capacity(KVA) | 6 | 10 | 15 | 30 | 100 | 200 | 450 | 600 | 800 | 1600 | |||
Circuit model | IGBT/SPWM pulse width adjustment mode | ||||||||||||
Output | 50Hz/60Hz 45-65Hz | ||||||||||||
Load stability | ≤±1% | ||||||||||||
frequency stability | fixed-frequency≤±0.01%,frequency modulation≤±0.1% | ||||||||||||
Input voltage | 220V±10% | 380V±10% | |||||||||||
Phase | single phase | three phase four wire | |||||||||||
Wave distortion | ≤3% | ||||||||||||
Output voltage | 1 - 500 V continuous-tuning | ||||||||||||
Reaction time | ≤2mS | ||||||||||||
DPI ( dots per inch ) | frequency meter | 0.1Hz | |||||||||||
Voltage meter | 0.1V | ||||||||||||
Current meter | 0. 1A | ||||||||||||
Power meter | 0.1W | ||||||||||||
Ammeter display | Frequency, voltage, current, power or PF 4 number display | ||||||||||||
Protection function | over voltage, over current, over temperature, over load, short circuit, and automatic alarm | ||||||||||||
Insulation reactance | 500Vdc 20MΩ | ||||||||||||
Pressure endurance insulation | 1500Vac/5mA/1min | ||||||||||||
Cooling model | Compulsive fan cooling | ||||||||||||
Working temperature | -10ºC-45ºC | ||||||||||||
Relative humidity | 0-90%(No condensing) | ||||||||||||
Altitude | 1500meters | ||||||||||||
Dimension (W×L×H)mm | 660*400*700 | 450*900*900 | 500*1100*1100 | 1320*600*1490 | 850*1450*1880 | 1160*1910*1880 | 1260*2000*2080 | 830*3262*2260 | |||||
model | 333000 | 3350000 | 33100000 | |
Capacity(KVA) | 3000 | 5000 | 10000 | |
Input | Voltage | 400V±15% 3phase 4wires or 3phase 5wires | ||
Frequency | 45-65Hz | |||
Power Factor | ≥0.90 | |||
Output | Voltage | 3phase 3 wires ,voltage(300-500V/690)can be chosen | ||
Frequency | 50Hz/60Hz can be chosen | |||
Frequency Stability | ≤0.01%(0-100% when load are changing,output frequency are not changing ) | |||
Load Stability | ≤3%(100% pure resistance load) | |||
Overload Ability | 110% 1hour ,150% 10minutes | |||
Wave Distortion | Pure sine wave,THD≤3% | |||
Efficiency | ≥90%(100% loads) | |||
Display | Input/output voltage/ frequency,3phase phase voltage/current,active power .working time.history error etc. | |||
Control mode | IGBT/SPWM Pulse width adjustment mode | |||
Protection Class | IP54 | |||
Insulation Reactance | >2MΩ | |||
Pressure endurance Insulation | 1800Vac/5Ma/1minute | |||
Noise Level | 50dBA @1meter | |||
Cooling Model | Converter:heat pipe cooling transformer:Compulsive fan cooling | |||
Protection Function | The output power supply have perfect protection function of over voltage, over current, short circuit, converter overheat . Consider the different control of the ship's electricity load, when the output load capacity reach the set value,will alarm, so as to control the electricity load | |||
Environment | -10ºC~+50ºC and 0~90% |