Item | 10ft | 20ft | 40ft |
DC input parameters | |||
Single model | LFP-220Ah | LFP-220Ah | LFP-320Ah |
Module model | 1P8S | 1P8S | 1P9S |
System configuration | 2*1P240S | 4*1P240S | 8*1P225S |
Initial battery nominal energy | 300kWh | 700kWh | 1300kWh |
Battery voltage range | 692V~838V | 692V~838V | 630V~810V |
AC output parameters | |||
AC rated power | 120kW | 240kW | 500kW |
Rated voltage | 400V±15% | ||
Rated frequency | 50Hz | ||
Grid frequency range | 47~52Hz | ||
Maximum harmonic current | ≤3% | ||
Battery compartment protection class | IP54 | ||
Protection class of PCS compartment | IP34 | ||
Operating temperature range | -10ºC~50ºC | ||
Maximum working altitude | <2000m | ||
Cooling method of battery compartment | HVAC | ||
ESS container fire fighting system | HFC-227eaFire Extinguishing system | ||
Communication interface | Ethernet | ||
Communication protocol | Modbus TCP/IP | ||
Container Size | 10/20/40ft | ||
ax containers in parallel | βMWh (Customized based on your installation site) |
1. | Pre sale service |
a. | make technical solution |
b. | send quotation, technical data sheet and drawing |
c. | prepare power transmission plan, testing plan and shipment plan |
2. | In sale service |
a. | supervise the manufacturing schedule totally in accordance with the plan |
b. | send photos to customer during every manufacturing process(hold point) |
c. | inform the customer one week before testing. |
3. | After sale service |
a. | installation and commissioning, training the workers |
b. | quick response within 12 hours any time |
c. | provide 12 months guarantee period normally. |