GT-WKR Series-Roof Top AHU Specifiaction 1 |
Model GT-WKR- | 10 | 15 | 18 | 20 | 25 | 30 | 35 |
|
Specification | Cooling capacity 1* | kW | 10.5 | 15.0 | 18.5 | 21.0 | 26.3 | 29.8 | 35.0 |
Heating capacity 2* | kW | 11.5 | 15.9 | 19.5 | 22.1 | 27.6 | 32.6 | 37.1 |
Supply air 3* | m3/h | 1800 | 2400 | 2900 | 3500 | 4500 | 5000 | 5800 |
Static pressure 3* | Pa | 100 | 150 | 150 | 180 | 200 | 250 | 250 |
Noise 4* | dB(A) | 60 | 60 | 62 | 62 | 65 | 65 | 68 |
Power | 3N-380V-50Hz |
Total capacity | 3.9 | 5.74 | 7.0 | 8.27 | 9.96 | 11.0 | 14.15 |
Color | White |
ooling system | Compressor | Type | Efficient scroll closed |
Quantity | 1 | 1 | 1 | 1 | 1 | 1 | 2 |
Supply air fan | Type | Low noise centrifugal type |
Capacity | kW | 0.37 | 0.55 | 0.75 | 0.75 | 1.1 | 1.5 | 2.2 |
Evaporator | Type | Inner grooved copper tube and aluminum fin |
Fin type 5* | Slotted fin hydrophilic aluminum fin |
Condenser | Type | Inner grooved copper tube and aluminum fin |
Fin type 5* | Rippled hydrophilic aluminum fin |
Condenser fan | Type | Low noise axial type |
Quantity | 1 | 1 | 1 | 1 | 1 | 1 | 2 |
Refrigerant | Refrigerant | R22/R407C |
Refrigerant control | External balance type thermal expansion valve |
Air filter | Initially effect plate filter |
Dimensions | L | mm | 1400 | 1400 | 1600 | 1600 | 1850 | 1850 | 2200 |
W | mm | 1050 | 1050 | 1200 | 1200 | 1400 | 1400 | 1800 |
H | mm | 1050 | 1050 | 1050 | 1050 | 1200 | 1200 | 1520 |
Weight | kg | 200 | 230 | 260 | 300 | 550 | 600 | 850 |