ITEM | 1-32 Zone panel | 2Zone panel | 4-8 Zone panel | 12-32 Zone panel |
Model No. | AW-CFP2166-01-32 | AW-CFP2166-02 | AW-CFP2166-04-8 | AW-CFP2166-12-32 |
Power specification | ||||
Mains supply voltage | 110VAC or 240VAC | |||
Internal power supply | 27.2VDC | |||
Total output current limited | 500mA @ 240VAC | 500mA @ 240VAC | 3A @ 240VAC | 3A @ 240VAC |
Main supply monitor for fault | Yes | |||
Battery protection for low voltage | Yes | |||
Batteries (default configuration) | 12V2AH*2 | |||
Detector circuit specification | ||||
Number of circuit | 1 | 2 | 4-16 | 4-32 |
Line fault monitor for open circuit | Yes | |||
Line fault monitor for short circuit | Yes | |||
Line fault monitor for detector removal | Yes, if End of Line Monitor Unit fitted in place of End of Line Resistor | |||
End of Line device | 6.8k Ω,5% tolerance, 0.25W (colour code-blue,grey,red,gold) | |||
Detector continuity diodes | Silicon 1N4001 or Schottky type (required if End of Line Monitor Unit fitted to give Detector Removal Fault) | |||
Call point resistor value | 470 to 680 Ω, 0.225 or 0.5 watt | |||
Maximum number of smoke/heat detectors per zone | 20 (based on a total detector current of 2mA, each detector consuming 100μA).Note: if End of Line Monitor Unit is fitted, for correct operation maxmum voltage drop must not exceed 12 volts. | |||
Maximum number of manual call points per zone | No limit | |||
Sounder circuit specification | ||||
Number of general circuits | 2 | |||
End of line resistor value | 6.8k Ω,5% tolerance, 0.25W (colour code-blue,grey,red,gold) | |||
Line fault monitor for open circuit | Yes | |||
Line fault monitor for short circuit | Yes | |||
Outputs fused AT | 400mA | |||
Maximum number of bells @ 20mA of each sounder output | 20 | |||
Fuses | ||||
Battery fuse | 1.5A F 20mm | |||
Sounder outputs | 500mA F 20mm | |||
Fire and fault output | ||||
Output type | NC and NO relay | |||
Maximum current | 100mA | |||
Connection block | ||||
Largest acceptable conductor size | 2.5mm2 | |||
Smallest acceptable conductor size | 0.75mm2 | |||
Size and weight | ||||
Dimensions(mm) | 272*200*70mm | 320*231*90mm | 395X502X124 | 362X565X124 |
Weight (without batteries) | 4kg | 5kg | 7kg | 8kg |
Weight (with batteries) | 5.8kg | 6.8kg | 9.6kg | 12.5kg |
Our company
Asenware, manufacturer of fire alarm and fire suppression system since 2005. Our headquarter is in London, UK, with factory Shenzhen, China
We keep our best service for our customers, and have a rich experienced engineer team to design and install for overseas projects.
Product range:
1. Addressable fire alarm system(FP100 series,2189,2100 series)
2. Conventional fire alarm system(2166 series)
3. FM200 gas fire suppression system
4. Emergency light system
5. Fire pump system
6. Fire hose and fire hose reel cabinet
Welcome contact