Mini Circuit Breaker with High Breaking Capacity (DC circuit)

Min.Order: 1
Product origin: Wenzhou, Zhejiang, China
Infringement complaint: complaintComplaint
US$ 10

Description

Aplication
The products of SM600 belong to the advanced level of the nineties in the international instead of the older generation of DZ47. They have protective function as shortage as overload are used in lighting distribution system in dndusty, commerce and etc. They also have many merits of high protective grade(up to IP20), high breaking capacity, reliable sensityve action, convenient, multipole assembing, long life etc. They are mainly adapted to the circuit of AC 50Hz, 230V in single pole, 400V in doulbe, three, four poles for protecting overload and short circuit. Meanwhile, they are also used in truning on or off the electric apparatus and lighting circuit under the normal condition.




 
It's applied for the overload, short circuit protection in DC circuit, esp. in the communication, electricity, engine etc.  
 
Rated breaking capacity 6000, C curve, instantaneous tripping 5~10In
 
Rated voltage(A)
Type
Type
 
 

 

1
ADDB7-1/1/1-/C-DC
ADDB7-1/2/1-/C-DC
2
ADDB7-2/1/1-/C-DC
ADDB7-2/2/1-/C-DC
3
ADDB7-3/1/1-/C-DC
ADDB7-3/2/1-/C-DC
4
ADDB7-4/1/1-/C-DC
ADDB7-4/2/1-/C-DC
6
ADDB7-6/1/1-/C-DC
ADDB7-6/2/1-/C-DC
10
ADDB7-10/1/1-/C-DC
ADDB7-10/2/1-/C-DC
16
ADDB7-16/1/1-/C-DC
ADDB7-16/2/1-/C-DC
20
ADDB7-20/1/1-/C-DC
ADDB7-20/2/1-/C-DC
25
ADDB7-25/1/1-/C-DC
ADDB7-25/2/1-/C-DC
32
ADDB7-32/1/1-/C-DC
ADDB7-32/2/1-/C-DC
40
ADDB7-40/1/1-/C-DC
ADDB7-40/2/1-/C-DC
50
ADDB7-50/1/1-/C-DC
ADDB7-50/2/1-/C-DC
63
ADDB7-63/1/1-/C-DC
ADDB7-63/2/1-/C-DC
   
  
Rate voltage of single pole 250V T=4msrate voltage of couple pole. 250V T=4ms
Overload current tripping characteristic
Code
 
Rated current In(A)
Start state
Testing current (A)
Limited current
Appointed resalt
a
B,C,D
≤63
cold state
1.13In
≤1h
non-trip
b
B,C,D
≤63
following up the A type test
1.45In
<1h
trip
c
B,C,D
≤63
cold state
2.55In
>1s~<60s
trip
>32
>1s~<120s
d
B
all
cold state
3In
≥0.1s
non-trip
C
5In
D
10In
e
B
alls
cold state
5In
0.1s
trip
C
10In
D
20In
Tripping characteristic curve
B characteristicC characteristicD characteristic

 

loading capacity curve ( for example 1 pole)
loading ability value
 
 

the allowed load in the operating state for the related temperature controller and n switches: IDL=InKT(T)Kn(N).

Circuit break of energy consumptipn
the current of short circuit
the current of short circuit
the max energy consumption of B characteristic single pole
the max energy consumption of C characteristic single pole

 

Product Tag:
Related categories: