Power supply: | |
Nominal voltage | DC 24V |
Operating limits | DC 20.4-28.8V |
Immunity from micro power cuts | Typ.5 ms |
Max. Startup current | Max. 0.3A |
Max. absorbed power | 10W |
Protection against polarity inversions | Yes |
Input parameters: | |
Input No | 16 ( I1-IG) |
Digital input | 16 ( I1-IG) |
Analogue input | 8 ( I1-I8)(0..10V DC) +4(ID-IG)(0...20mA OR 0..10V DC) |
Digital input and analog inputs (0...10V)10bits( I1-I8 ) | |
Inputs used as digital inputs( I1-I8 ) | |
Input voltage | DC0-28.8V |
Input signal0 | < 5V DC;<0.08mA |
Input signal1 | > 8 V DC;>0.12mA |
Input current | 0.16mA @ 10.8V dc 0.18mA @ 12.0 V dc 0.34mA @ 24 V dc 0.41mA @ 28.8 V dc |
Response time | 0 to 1 :Typ. 10.5 ms ;1 to 0 :Typ. 1.5 ms |
Maximum counting frequency | Typ.:4 HZ |
Sensor type | Contact or 3-wire PNP |
Input type | Resistive |
Isolation between power supply and inputs | None |
Isolation between inputs | None |
Inputs used as analog inputs(0..10V)( I1-I8 ) | |
Measurement range | DC 0---10V |
Input impedance | Min, 24KΩ; Max. 72KΩ |
Input voltage | 28.8 V DC max |
Resolution | 10bit ,0.01V |
Accuracy at 25 °C | ± (Max.0.02)V |
Accuracy at 55 °C | ± (Max.0.04)V |
Isolation between analog channel and power supply | None |
Cable length | 10 m max. shielded and twisted |
Digital and high speed inputs(I9--IC) | |
Digital inputs( I9-IC ) | |
Input voltage | DC0-28.8V |
Input signal0 | < 5V DC; <1mA |
Input signal1 | > 8 V DC;>1.6mA |
Input current | 2.1mA @ 10.8V dc 2.3mA @ 12.0 V dc 4.6 mA @ 24 V dc 5.5 mA @ 28.8 V dc |
Response time | 0 to 1 :<1 ms ;1 to 0 :<1 ms |
High speed inputs( I9-IC ) | |
Maximum counting frequency | 60kHZ(I9--IC) |
Digital and analog(0--10V)&analog(0...20mA)(ID-IG) | |
Inputs used as digital inputs( ID-IG ) | |
Input voltage | DC0-28.8V |
Input signal0 | < 5V DC;<0.08mA |
Input signal1 | > 8 V DC;>0.12mA |
Input current | 0.16mA @ 10.8V dc 0.18mA @ 12.0 V dc 0.34mA @ 24 V dc 0.41mA @ 28.8 V dc |
Response time | 0 to 1 :Typ. 10.5 ms ;1 to 0 :Typ. 1.5 ms |
Maximum counting frequency | Typ.:4 HZ |
Sensor type | Contact or 3-wire PNP |
Input type | Resistive |
Isolation between power supply and inputs | None |
Isolation between inputs | None |
Inputs used as analog inputs(0..10V)( ID-IG ) | |
Measurement range | DC 0---10V |
Input impedance | Min, 24KΩ; Max. 72KΩ |
Input voltage | 28.8 V DC max |
Resolution | 10bit ,0.01V |
Accuracy at 25 °C | ± (Max.0.02)V |
Accuracy at 55 °C | ± (Max.0.04)V |
Isolation between analog channel and power supply | None |
Cable length | 10 m max. shielded and twisted |
Input signal0 | < 5V DC;<0.08mA |
Input signal1 | > 8 V DC;>0.12mA |
Input current | 0.16mA @ 10.8V dc 0.18mA @ 12.0 V dc 0.34mA @ 24 V dc 0.41mA @ 28.8 V dc |
Response time | 0 to 1 :Typ. 10.5 ms ;1 to 0 :Typ. 1.5 ms |
Sensor type | Contact or 3-wire PNP |
Input type | Resistive |
Isolation between power supply and inputs | None |
Isolation between inputs | None |
Inputs used as analog inputs(0..20mA)( ID-IG ) | |
Analogue signal | 0/4….20mA current |
Input impedance | 260Ω |
Resolution | 0.02mA |
Accuracy at 25 °C | 0.05mA |
Cycle time for analog value generation | Typ. 50 ms |
Protection against polarity inversions | yes |
Overvoltage protection | Yes, if the input voltage is >6.5V, this one is automatically switched on 0--10V configuration |
Isolation between power supply and inputs | No |
Cable length | <=30M with shielded twisted cable(sensor not isolated) |
Output (2 Analog output + 8 Relay output) | |
Analog output(0...10V)/Analog output(0...20mA):AQ1--AQ2(Can be switched for voltage or current output) | |
Output No. | 2 (AQ1-AQ2) |
Output signal | DC 0…10V |
Internal value and signal relationship | AQ1/AQ2(0..1000)= V1(0...10V) |
Resolution | 0.01V |
Accuracy at 25 °C | 0.02V |
Output signal | 0..20mA |
Internal value and signal relationship | AQ1/AQ2(0...1000)= I1(0...20mA) |
Resolution | 0.02mA |
Accuracy at 25 °C | 0.05mA |
5A Relay 4 outputs from Q3 to Q6 | |
Max. breaking voltage | CE:AC 250 V/DC 30 V 5A UL:AC 250 V/DC 30 V 3A |
Electrical durability Expectancy | 105 Operations at Rated Resistive Load |
Mechanical life | 107 Operations at No Load condition |
Response time | Operate Time: 15 mSec. Max. Release Time: 10 mSec. Max. |
Built-in protections | Against short-circuits: None Against overvoltages and overloads: None |
10A Relay 4 outputs from Q7 to QA | |
Max. breaking voltage | CE:AC 250 V/DC 30 V 10A UL:AC 250 V/DC 28 V 5A |
Max. Allowable Power Force | 1250VA |
Electrical durability Expectancy | 105 Operations at Rated Resistive Load |
Mechanical life | 107 Operations at No Load condition |
Response time | Operate Time: 15 mSec. Max. Release Time: 10 mSec. Max. |
Built-in protections | Against short-circuits: None Against overvoltages and overloads: None |
Communication ports parameters: | |
COM0_TTL port | Can be used as program port with PR-RS232&PR-USB; Also can be convert to RS232 port with PR-RS232 Can be convert to RS485 port with PRO-RS485 Note:Need move away the expand cover to use it Can be used as modbus master or slave |
Built-in RS485 COM2 | 1 built-in RS485 port (Terminal A+,B-) Can be used as modbus master or slave |
Built-in RS485 COM3 | 1 built-in RS485 port (Terminal A+,B-) Can be used as modbus master or slave |
Ext RS485 COM1 | Need use with PR-E-RS485 module Can be used as modbus master or slave |
Ethernet port: | Built-In(10M/100M), 1.Can be used as program or communication 2.Can be used as modbus master or slave |
Monitoring webserver page | Yes |
Xlogic<--->Xlogic(by Ethernet) | 1 xlogic works as tcp server can connect with 8 tcp client xlogics or other tcp devices. |
Xlogic<--->Ethernet/Internet: | 1 xlogic works as TCP clients can connect with 8 different tcp servers separately in maximum |
Other parameter | |
Weight | Approx.400g |